Inspections for the day of: Thursday, December 14, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04313 FIRE-Final Inspection12/14/201712/14/201712/14/2017 2:11:38 PMPFAIL
No city approved plans or notes on site. Need the GRD permit inspected/finaled. I did test all of the smoke alarms and verified fire extinguishers. Per conversation with Ron Johnson an address monument will be needed at the entrance to show the interior building addresses for the responding personell.

Phone #: ###-#### Inspection requested via web by David Scaggs
BLD16-04314 FIRE-Final Inspection12/14/201712/14/201712/14/2017 2:11:19 PMPFAIL
No city approved plans or notes on site. Need the GRD permit inspected/finaled. I did test all of the smoke alarms and verified fire extinguishers. Per conversation with Ron Johnson an address monument will be needed at the entrance to show the interior building addresses for the responding personell.

Phone #: ###-#### Inspection requested via web by David Scaggs
FIR17-00417 INSP-Final Inspection12/14/201712/14/201712/14/2017 1:50:31 PMPFAIL
As-builts did not match install

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00416 INSP-Final Inspection12/13/201712/14/201712/14/2017 1:50:13 PMPFAIL
As-builts did not match install

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00415 INSP-Final Inspection12/14/201712/14/201712/14/2017 1:49:55 PMPFAIL
As-builts did not match install

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00414 INSP-Final Inspection12/14/201712/14/201712/14/2017 1:49:36 PMPFAIL
As-builts did not match install

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00727 INSP-Final Inspection12/13/201712/14/201712/14/2017 10:55:44 AMAFAIL
Panel and devices passed, smoke and pull tested ok, phone lines tested ok, the 30cd ceiling mount near the facp needs to be relocated or adjusted to a 75cd, a strobe needs to be added in the area just outsside of the facp, as-builts are needed to show these changes, sprinkler devices not tested due to no sprinkler contractor on site. Randy is going to email verification of the signals sent.

FIR17-00727 Phone #: ###-#### Inspection requested via web by Bruce Sullivan
BLD17-03470 FIRE-Final Inspection12/13/201712/14/201712/14/2017 9:56:00 AMAPASS
life safety passed

Phone #: ###-#### Inspection requested via web by Gerome Fries
BLD15-02939 FIRE-Final Inspection12/13/201712/14/201712/14/2017 9:17:02 AMAFAIL
Called contact and left message that I was on the way. Arrived and made no contact and found project locked with no access. No inspection performed.

Phone #: ###-#### Inspection requested via web by SHANE JAYO
BLD17-01446 FIRE-Final Inspection12/13/201712/14/201712/14/2017 8:57:43 AMAFAIL
Provide correct suite number, provide permit for sprinkler modifications (one pendant is too close to wall/contractor states Phoenix pulled permit for work), provide missing canopies, provide fire alarm permit for additional devices or demo, mount the fire extinguishers.

Braven Phone #: ###-####
BLD17-00471 FIRE-Final Inspection12/13/201712/14/201712/14/2017 7:45:02 AMAPASS
Life safety passed

Butch Phone #: ###-####