BLD16-04313
| FIRE-Final Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 2:11:38 PM | P | FAIL |
|
|
No city approved plans or notes on site. Need the GRD permit inspected/finaled. I did test all of the smoke alarms and verified fire extinguishers. Per conversation with Ron Johnson an address monument will be needed at the entrance to show the interior building addresses for the responding personell.
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD16-04314
| FIRE-Final Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 2:11:19 PM | P | FAIL |
|
|
No city approved plans or notes on site. Need the GRD permit inspected/finaled. I did test all of the smoke alarms and verified fire extinguishers. Per conversation with Ron Johnson an address monument will be needed at the entrance to show the interior building addresses for the responding personell.
Phone #: ###-#### Inspection requested via web by David Scaggs
|
FIR17-00417
| INSP-Final Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 1:50:31 PM | P | FAIL |
|
|
As-builts did not match install
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00416
| INSP-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 1:50:13 PM | P | FAIL |
|
|
As-builts did not match install
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00415
| INSP-Final Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 1:49:55 PM | P | FAIL |
|
|
As-builts did not match install
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00414
| INSP-Final Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 1:49:36 PM | P | FAIL |
|
|
As-builts did not match install
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00727
| INSP-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 10:55:44 AM | A | FAIL |
|
|
Panel and devices passed, smoke and pull tested ok, phone lines tested ok, the 30cd ceiling mount near the facp needs to be relocated or adjusted to a 75cd, a strobe needs to be added in the area just outsside of the facp, as-builts are needed to show these changes, sprinkler devices not tested due to no sprinkler contractor on site. Randy is going to email verification of the signals sent.
FIR17-00727 Phone #: ###-#### Inspection requested via web by Bruce Sullivan
|
BLD17-03470
| FIRE-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 9:56:00 AM | A | PASS |
|
|
life safety passed
Phone #: ###-#### Inspection requested via web by Gerome Fries
|
BLD15-02939
| FIRE-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 9:17:02 AM | A | FAIL |
|
|
Called contact and left message that I was on the way. Arrived and made no contact and found project locked with no access. No inspection performed.
Phone #: ###-#### Inspection requested via web by SHANE JAYO
|
BLD17-01446
| FIRE-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 8:57:43 AM | A | FAIL |
|
|
Provide correct suite number, provide permit for sprinkler modifications (one pendant is too close to wall/contractor states Phoenix pulled permit for work), provide missing canopies, provide fire alarm permit for additional devices or demo, mount the fire extinguishers.
Braven Phone #: ###-####
|
BLD17-00471
| FIRE-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 7:45:02 AM | A | PASS |
|
|
Life safety passed
Butch Phone #: ###-####
|