Inspections for the day of: Thursday, December 20, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00926 INSP-Sprinkler Rough-in12/19/201812/20/201812/20/2018 3:28:08 PMPPASS
Early rough-in passed.


Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00856 INSP-Final Inspection12/19/201812/20/201812/20/2018 3:27:38 PMAPART
We tested the new dry pipe valves which passed. The nitrogen gererator is installed but is cycling excesivly as per discussion with the sprinkler contractor. I have contacted my supervisory and the fire dept for guidance.

Phone #: ###-#### Inspection requested via web by Chris Gregory
FIR18-00901 INSP-Sprinkler Rough-in12/20/201812/20/201812/20/2018 2:51:16 PMPPASS
Cover inspection for IBR Stub out passed. Piping/IBR can be covered.

Please call ROY, with time frame. Thanks and have a great day. Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR18-00913 INSP-Sprinkler Rough-in12/19/201812/20/201812/20/2018 2:02:50 PMPFAIL
No underground supply piping has even been installed yet per the general contractor


Contact Keith Orahood ###-#### 30 Min prior to UG RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00128 INSP-Sprinkler Rough-in12/18/201812/20/201812/20/2018 1:47:18 PMPFAIL
Was only able to do a partial inspection due to numerous pipe routing changes. I also noted that alot of additional fittings have been added that might affect the hydraulic calculations. I also noted tenting issues in the garage area. Contractor will need to contact plan review and see if as-builts or plan modifications are required. This will need to be done prior to another inspection being scheduled. Per the general contractor blow-in insulation will be used above the ceilings in the garage.

Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
FIR18-00510 INSP-Sprinkler Rough-in12/19/201812/20/201812/20/2018 12:46:19 PMACANC
Cancel per Brian

Town homes Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-02535 FIRE-Final Inspection12/19/201812/20/201812/20/2018 11:27:27 AMACANC
Not ready per Sarah Phone #: ###-####
FIR18-00731 INSP-Final Inspection12/19/201812/20/201812/20/2018 11:11:39 AMACANC
Went to project but it was not ready.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00491 INSP-Final Inspection12/19/201812/20/201812/20/2018 11:09:49 AMACANC
Went to project site but it is not ready.


Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00814 INSP-Sprinkler Rough-in12/19/201812/20/201812/20/2018 10:19:05 AMAPART
Tenting and rough in passed for the most part. One area in the Master Bedroom needs tenting repaired prior to cover and cpvc piping compatibility with the insulation spray foam needs to be verified prior to cover on any of the vertical sprinkler lines. All other areas can be covered. The control valve under the riser needs to be removed


. Please call about an hour ahead so me and the contractor can meet with you. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00603 INSP-Sprinkler Rough-in12/19/201812/20/201812/20/2018 9:22:22 AMAPASS
The piping above the two south side restrooms is ok for cover.
NAF18-00127 INSP-Final12/18/201812/20/201812/20/2018 6:52:06 AMADONE
Permit finaled


6:30 AM inspection for Fred Meyer in Garden City. Store opens at 7am. Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR18-00767 INSP-Final Inspection12/17/201812/20/201812/18/2018 9:43:30 AMACANC
This inspection will be with our technician Eric Nelson ###-####. Phone #: ###-#### >> Inspection requested via web by Cheyenne Zumstein Inspection cancelled from web by: Cheyenne Zumstein