Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00557 INSP-Sprinkler Rough-in12/22/201612/22/201612/22/2016 1:21:15 PMPPART
The hardlids on the first floor are ok to cover. I noted that branchline restraints are missing and that the plans need to be resubmitted for a plan modification due to pipe routing changes/additional fittings. See note on plan sheet two. The designer contacted me and we spoke of the changes.
FIR16-00670 INSP-Final Inspection12/21/201612/22/201612/22/2016 11:11:38 AMAPASS
permit finaled