BLD18-03931
| FIRE-Final Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 1:38:36 PM | P | FAIL |
|
|
Sprinkler modifications are needed for fire sprinkler coverage
Please call ahead 10 so i can meet you. Phone #: ###-#### Inspection requested via web by Todd Landvatter
|
BLD18-04373
| FIRE-Final Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 12:46:19 PM | P | CANC |
|
|
Duplicate inspection
Kaylee Phone #: ###-####
|
FIR18-00913
| INSP-Sprinkler Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 12:45:39 PM | A | PASS |
|
|
Underground stub out is ok for cover.
rough to cover // Leroy Phone #: ###-####
|
BLD18-04373
| FIRE-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 11:59:24 AM | A | PASS |
|
|
Life safety passed
Kaylee ###-####-please call to meet
|
BLD18-01191
| FIRE-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 11:54:21 AM | A | FAIL |
|
|
Need two exit signs repaired, one emergency light, need both ends of the fie dept access corrected/approved (gate is not 20' clear, pavement is not 20', and permanant bollards at the south end)
###-#### Inspection requested via web by Markus Schlegel
|
FIR18-00592
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 11:37:42 AM | A | PASS |
|
|
permit finaled
Ken Phone #: ###-####
|
FIR18-00566
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 11:37:20 AM | A | PASS |
|
|
Permit finaled
|
FIR18-00590
| INSP-Final Inspection | 12/26/2018 | 12/28/2018 | 12/28/2018 11:36:49 AM | A | PASS |
|
|
Permit finaled
Andrew Phone #: ###-####
|
FIR18-00569
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 11:36:04 AM | A | FAIL |
|
|
Need as-builts/plan mods for all of the candella changes, need to discuss Entry way notification with plan review and add if required, need weather proof backbox in Dishwashing area on the speaker strobe, need to verify phone lines, need to verify equipment and batteries, need to verify dedicated circuit, need to verify function of notification.
Ken Phone #: ###-####
|