Inspections for the day of: Monday, December 3, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02673 FIRE-Final Inspection12/3/201812/3/201812/3/2018 3:31:26 PMPPASS
Life safety passed.

Adam Phone #: ###-####
FIR18-00823 INSP-Sprinkler Rough-in12/3/201812/3/201812/3/2018 3:19:50 PMPPASS
Rough-in passed. Piping is ok for cover.

John Phone #: ###-####
FIR18-00896 INSP-Sprinkler Rough-in12/3/201812/3/201812/3/2018 2:13:52 PMPPASS
The underground supply piping to the four buildings is ok for cover.


underground // Andy Phone #: ###-####
FIR18-00879 INSP-Sprinkler Rough-in12/3/201812/3/201812/3/2018 1:51:14 PMPPART
Rough-in passed and the piping can be covered. The sprinkler pendant in the restroom needs replaced due to being painted.


Richard is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00837 INSP-Sprinkler Rough-in12/3/201812/3/201812/3/2018 12:58:20 PMPPART

Piping is ok to cover but the new branchline is shown to be 1 1/4" and has been installed as 1". Also this new line needs a branch line restraint.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00769 INSP-Sprinkler Rough-in12/3/201812/3/201812/3/2018 12:08:20 PMPPASS
Rough-in passed. Piping can be covered.

Tom Phone #: ###-####
BLD18-02510 FIRE-Conference12/3/201812/3/201812/3/2018 12:07:46 PMPDONE
We discussed lowering the ceiling mounted strobes to the lowere "clouds" and fire extinguisher placement.

Phone #: ###-#### Inspection requested via web by David Sferle
FIR18-00807 INSP-Final Inspection12/3/201812/3/201812/3/2018 12:06:46 PMPPASS
Permit finaled

RICK FRY Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD18-01139 FIRE-Final Inspection11/30/201812/3/201812/3/2018 11:26:13 AMAPART
Life safety passed for the two PICU rooms.

Kelly Phone #: ###-####
FIR18-00890 INSP-Final Inspection11/28/201812/3/201812/3/2018 10:37:22 AMAPASS
Permit finaled


Radio-Jason Phone #: ###-####
BLD18-01160 FIRE-Final Inspection11/30/201812/3/201812/3/2018 9:41:18 AMAPASS
Life safety passed.

joesph Phone #: ###-####
BLD18-03000 FIRE-Final Inspection11/30/201812/3/201812/3/2018 9:40:36 AMAFAIL
Life safety will be ok to pass when the fire alarm issue is resolved for the overspace stobe on the ground level south/east corner.

Phone #: ###-#### Inspection requested via web by Ryan Wilhelm
BLD18-02996 FIRE-Final Inspection11/30/201812/3/201812/3/2018 9:39:35 AMAFAIL
Provide new fire hydrant as referenced under the review notes and BLD18-01396, provide a fire extinguisher, min. 4A with current inspection tag as discussed, remove the thumbturn deadbolt. Keyed is ok with indicator and sticker. Lever hardware can be provided as long as it is single action ADA type. Building not to be used until approved.

Chris Phone #: ###-####
FIR18-00464 INSP-Sprinkler Rough-in11/29/201812/3/201812/3/2018 8:52:10 AMACANC
The building dept needs to approved the plan modifications prior to a fire sprinkler inspection for these areas.

doghouses Phone #: ###-#### Inspection requested via web by Matthew Lewis