Inspections for the day of: Tuesday, December 31, 2013.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-02637 FIRE-Final Inspection12/30/201312/31/201312/31/2013 3:33:37 PMAPART
A temporary occupancy was given with Romeo's permission until the project related fire alarm permit has been finaled.
FIR13-00672 INSP-Final Inspection12/31/201312/31/201312/31/2013 3:31:21 PMPPART
A temporary was given with Romeo's permission. At issue are the strobes whose effect can not be seen in all areas as required in NFPA 72 sections 18.5.4.1 through 18.5.4.3
BLD13-03148 FIRE-Final Inspection12/31/201312/31/201312/31/2013 2:15:24 PMPPASS
life safety passed. Per Carl Madsen in plan review the fire doors are not required for this occupancy. Also the existing fire alarm system was removed by Alarm Star without a permit. But it appears, from discussion with scott arellano, that the system is not required for this occupancy.
FIR13-00707 INSP-Final Inspection12/31/201312/31/201312/31/2013 11:08:35 AMPPASS
permit finaled
BLD13-03280 FIRE-Final Inspection12/31/201312/31/201312/31/2013 11:06:57 AMPPASS
life safety passed
FIR13-00665 INSP-Final Inspection12/30/201312/31/201312/31/2013 10:27:12 AMAPASS
permit finaled
FIR13-00187 INSP-Alarm Testing12/30/201312/31/201312/31/2013 10:11:27 AMADONE
Todays inspection was for the remaining notification device function. All devices tested ok except a horn only was installed where a strobe is shown in a corridor in the Auditorium and there was one non-functional ceiling mounted strobe in the east main lobby restroom of the Gym.