Inspections for the day of: Thursday, February 1, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02915 FIRE-Final Inspection2/1/20182/1/20182/1/2018 3:17:57 PMPFAIL
Provide fire extinguisher on the mezzanine, provide a exit discharge light at the main exit, provide double door with panic hardware at the rear exit as per the T.I. plans

Hugo Phone #: ###-####
BLD17-01548 FIRE-Conference2/1/20182/1/20182/1/2018 3:02:36 PMPDONE
We discussed life safety items such as possible exit discharge lighting and interconnection of the access control egress locks with the new fire alarm system
FIR17-00733 INSP-Conference2/1/20182/1/20182/1/2018 2:34:37 PMPDONE
We dicussed strobe modifications in the first floor lobby and in the basement.


John Phone #: ###-####
BLD17-03247 FIRE-Final Inspection1/31/20182/1/20182/1/2018 2:26:46 PMAFAIL
Need the project related fire alarm permit addressed. Will be ok for a temp when the fire alarm permit is finaled. For a final, the exit discharge light above the front exit will need to be installed.

Byron Phone #: ###-####
FIR17-00352 INSP-Final Inspection1/31/20182/1/20182/1/2018 1:54:56 PMPPASS
Permit finaled
BLD16-04308 FIRE-Final Inspection1/31/20182/1/20182/1/2018 1:54:36 PMAFAIL
Need smoke alarms to be located atleast 3' from fan blades and re-tested, need fees paid and inspection called in for the project related fire alarm permit. Need paint removed from the FDC.
FIR17-00453 INSP-Sprinkler Rough-in2/1/20182/1/20182/1/2018 12:33:33 PMPPASS
Underground Inspection passed. Piping can be covered.
FIR17-00450 INSP-Sprinkler Rough-in2/1/20182/1/20182/1/2018 12:33:05 PMPPASS
Underground Inspection passed. Piping can be covered
FIR17-00493 INSP-Sprinkler Rough-in2/1/20182/1/20182/1/2018 10:53:54 AMPCANC
underground inspection okay to cover Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
FIR17-00541 INSP-Sprinkler Rough-in1/31/20182/1/20182/1/2018 9:19:47 AMAPASS
24 hour air test passed. The remaining second floor piping rough-in passed. Piping can be covered. Plan Mod needed showing pipe routing changes for 3" mains and Pre-action system.