Inspections for the day of: Wednesday, February 13, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00086 INSP-Final Inspection2/13/20192/13/20192/13/2019 2:31:54 PMPFAIL
Need plan mods for deleting the ceiling mounted horn/strobe in the now Office and the device in the Restroom needs changed out to match the new devices so that the all function together


Please call 1/2 hour ahead of time Phone #: ###-#### Inspection requested via web by Rafe Barrett
FIR17-00508 INSP-Final Inspection2/12/20192/13/20192/13/2019 1:48:23 PMPFAIL
As builds were missing some points and need updated,.
network addressing from new building to main needs to be fixed in order to show what building the alarm is coming from.
off site reporting does not work correctly. panel will send single alarm signal when panel is in trouble but will not restore or send other alarms till trouble is cleared. spoke with lee meridith and individual alarm/trouble/supervisory signals from panel to aes need to be set up qnd not single zone.
elevator recall and remote mic still need to be tested.
Area A TCO re-inspect Phone #: ###-#### Inspection requested via web by Shane Lesteberg
BLD18-03042 FIRE-Final Inspection2/13/20192/13/20192/13/2019 12:35:54 PMPPASS
life safety passed

Bob Phone #: ###-####
BLD18-02867 FIRE-Final Inspection2/12/20192/13/20192/13/2019 12:25:58 PMAFAIL
Provide a fire exitinguisher as discussed with current inspection tag

Call for lock box combo // Rob Phone #: ###-####
BLD17-02262 FIRE-Conference2/12/20192/13/20192/13/2019 12:03:42 PMACANC
Overall expectations project walk. Fire Extinguishers, Knox boxes, system setup, etc. Phone #: ###-#### Inspection requested via web by JT Turner
FIR19-00020 INSP-Final Inspection2/12/20192/13/20192/13/2019 10:56:02 AMAFAIL
This permit/scope of work is not ready. Wrong permit was called in.

Call Leon Taylor for final inspection on Bodega TI Phone #: ###-#### Inspection requested via web by Sheldon Gray
BLD18-01736 FIRE-Final Inspection2/12/20192/13/20192/13/2019 10:35:20 AMAPASS
Life safety passed

Phone #: ###-#### Inspection requested via web by Mark Steen
FIR18-00512 INSP-Final Inspection2/12/20192/13/20192/13/2019 10:23:19 AMAPASS
Underground supply line flush passed
BLD18-03208 FIRE-Final Inspection2/12/20192/13/20192/13/2019 9:31:29 AMACANC
I spoke to Tammy about racking permit requirements and that I could not find a fire sprinkler permit for the work done. Will be rescheduled.

Call for Tammy, she has the plans Phone #: ###-####
FIR18-00642 FIR-Aging Inspection2/13/20192/13/20192/13/2019 9:04:32 AMAFAIL
Not ready for final due to issues with hvac activation, need protecive cover for IP DACT, need cut sheet for FACP showing internal mounting for IP DACT, need fuel verification for generator, need to verify as-builts are correct (NAC's)
FIR19-00017 INSP-Sprinkler Rough-in2/12/20192/13/20192/13/2019 9:01:54 AMAPASS
Rough-in passed. Piping is ok for cover.

Rick Phone #: ###-####
FIR18-00642 INSP-Final Inspection2/12/20192/13/20192/13/2019 8:55:12 AMACANC
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Wednesday, February 13, 2019.