BLD19-00348
| FIRE-Final Inspection | 2/14/2019 | 2/14/2019 | 2/14/2019 1:55:10 PM | P | PASS |
|
|
Life safety passed
Mohamed Phone #: ###-#### please call for access
|
NAF18-00077
| INSP-Conference | 2/13/2019 | 2/14/2019 | 2/14/2019 1:24:07 PM | A | DONE |
|
|
The electrian and I discussed the placement of the smoke alarm in the two bedroom apartments. I would agree with the placement of the detector outside of the small Hallway that leads to the bedroom and the restroom as a solution to get the detector head 3' away from the restroom door.
Call prior to going Phone #: 2089571097 >> Inspection requested via mobile web by Todd Deike
|
FIR18-00435
| INSP-Sprinkler Rough-in | 2/13/2019 | 2/14/2019 | 2/14/2019 12:12:48 PM | A | PASS |
|
|
The south lobby is ok for cover. The hardlid ceiling just inside of the main west facing lobby is ok for cover. Missing earthquake bracing on te mains has been provided except in garage area which needs to be verified for weight as discussed. Sprinkler coverage has been provided under the stairs. It appears that the wall layout on the upper level does not match the sprinkler plans and will need to be modified
Josh Eaton is the contact. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00058
| INSP-Final Inspection | 2/13/2019 | 2/14/2019 | 2/14/2019 12:05:03 PM | A | FAIL |
|
|
Need to trip the dry pipe valve and possibly measure the trip time and verify quick opening device.
Nick Phone #: ###-####
|
FIR19-00056
| INSP-Final Inspection | 2/13/2019 | 2/14/2019 | 2/14/2019 12:02:58 PM | A | FAIL |
|
|
Heads are mounted too close to walls and missing hangers.
Nick Phone #: ###-####
|
FIR19-00057
| INSP-Final Inspection | 2/13/2019 | 2/14/2019 | 2/14/2019 12:01:25 PM | A | PASS |
|
|
Permit finaled
Nick Phone #: ###-####
|
FIR18-00642
| INSP-Final Inspection | 2/13/2019 | 2/14/2019 | 2/14/2019 9:32:06 AM | A | FAIL |
|
|
The hvac units did not shut down upon alarm activation as required per IMC 606.4, need the enclosure for the communicator installed.
As early as possible Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
|
BLD17-04134
| FIRE-Final Inspection | 2/13/2019 | 2/14/2019 | 2/14/2019 9:30:59 AM | A | FAIL |
|
|
Provide review comments, provide exit discharge lights at the two exits, the pizza oven must fit under the hood by 6" as per mechanical code, provide single action (lever type) hardware for doors 103A and 102A, remove both dead bolts at the main exit doors, provide panic hardware and exit light, exit sign, exit discharge light at door 106A or provide plan review approval of alternate (plans show area as a "M" but is currently being used as an "S").
Jake-please call 20 minutes prior to meet for access Phone #: ###-####
|
BLD18-04334
| FIRE-Final Inspection | 2/13/2019 | 2/14/2019 | 2/14/2019 9:27:55 AM | A | PASS |
|
|
Life safety passed
Taylor Phone #: ###-####
|
NAF18-00138
| INSP-Final | 2/13/2019 | 2/14/2019 | 2/13/2019 2:54:43 PM | A | CANC |
|
|
Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by Dave Inspection cancelled via mobile web on Wednesday, February 13, 2019.
|