Inspections for the day of: Thursday, February 14, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00348 FIRE-Final Inspection2/14/20192/14/20192/14/2019 1:55:10 PMPPASS
Life safety passed

Mohamed Phone #: ###-#### please call for access
NAF18-00077 INSP-Conference2/13/20192/14/20192/14/2019 1:24:07 PMADONE
The electrian and I discussed the placement of the smoke alarm in the two bedroom apartments. I would agree with the placement of the detector outside of the small Hallway that leads to the bedroom and the restroom as a solution to get the detector head 3' away from the restroom door.

Call prior to going Phone #: 2089571097 >> Inspection requested via mobile web by Todd Deike
FIR18-00435 INSP-Sprinkler Rough-in2/13/20192/14/20192/14/2019 12:12:48 PMAPASS
The south lobby is ok for cover. The hardlid ceiling just inside of the main west facing lobby is ok for cover. Missing earthquake bracing on te mains has been provided except in garage area which needs to be verified for weight as discussed. Sprinkler coverage has been provided under the stairs. It appears that the wall layout on the upper level does not match the sprinkler plans and will need to be modified

Josh Eaton is the contact. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00058 INSP-Final Inspection2/13/20192/14/20192/14/2019 12:05:03 PMAFAIL
Need to trip the dry pipe valve and possibly measure the trip time and verify quick opening device.

Nick Phone #: ###-####
FIR19-00056 INSP-Final Inspection2/13/20192/14/20192/14/2019 12:02:58 PMAFAIL
Heads are mounted too close to walls and missing hangers.

Nick Phone #: ###-####
FIR19-00057 INSP-Final Inspection2/13/20192/14/20192/14/2019 12:01:25 PMAPASS
Permit finaled

Nick Phone #: ###-####
FIR18-00642 INSP-Final Inspection2/13/20192/14/20192/14/2019 9:32:06 AMAFAIL
The hvac units did not shut down upon alarm activation as required per IMC 606.4, need the enclosure for the communicator installed.

As early as possible Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
BLD17-04134 FIRE-Final Inspection2/13/20192/14/20192/14/2019 9:30:59 AMAFAIL
Provide review comments, provide exit discharge lights at the two exits, the pizza oven must fit under the hood by 6" as per mechanical code, provide single action (lever type) hardware for doors 103A and 102A, remove both dead bolts at the main exit doors, provide panic hardware and exit light, exit sign, exit discharge light at door 106A or provide plan review approval of alternate (plans show area as a "M" but is currently being used as an "S").

Jake-please call 20 minutes prior to meet for access Phone #: ###-####
BLD18-04334 FIRE-Final Inspection2/13/20192/14/20192/14/2019 9:27:55 AMAPASS
Life safety passed

Taylor Phone #: ###-####
NAF18-00138 INSP-Final2/13/20192/14/20192/13/2019 2:54:43 PMACANC
Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by Dave Inspection cancelled via mobile web on Wednesday, February 13, 2019.