Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF18-00110 INSP-Conference2/20/20192/20/20192/20/2019 3:10:31 PMPCANC
Bruce would like to reschedule for morning at 7:30. Call prior to going Phone #: 2086065557 >> Inspection requested via mobile web by Bruce
FIR18-00946 INSP-Final Inspection2/18/20192/20/20192/20/2019 2:28:46 PMPFAIL
No actual testing performed. Plan mods are needed showing the actual fire alarm panel installed, a smoke detector is needed over the facp, provide verification whether hvac shutdown is needed or not, provide plan mods or make field changes to strobes that are overspaced, provide device map as per the review comments.

Nate Schneider is point of contact, please call roughly 15 minutes prior to arriving to site. ###-#### Phone #: ###-#### Inspection requested via web by jason petty
FIR18-00139 INSP-Final Inspection2/19/20192/20/20192/20/2019 2:00:25 PMPCANC
Not ready for a final yet. Missing ceiling tile and the project related fire alarm was not ready. Mike Phone #: ###-####
FIR18-00926 INSP-Sprinkler Rough-in2/19/20192/20/20192/20/2019 1:45:02 PMPCANC
Please call before heading out, thank you! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
BLD18-04569 FIRE-Final Inspection2/19/20192/20/20192/20/2019 10:40:20 AMPPASS
Life safety passed

Randy Phone #: ###-####
FIR18-00940 INSP-Final Inspection2/19/20192/20/20192/20/2019 10:14:13 AMAFAIL
Need the strobe in the restroom removed and as-builts provided.

Inspection needs to be done around 7:30am Phone #: ###-#### Inspection requested via web by Rafe Barrett
NAF18-00138 INSP-Final2/19/20192/20/20192/20/2019 10:13:36 AMAFAIL
Provide indicators on the two new doors, provide sticker on the two new doors, repair rear exit door exit sign, provide verification of need of sprinkler protection at bottom of stairs in front of new tenant door. May need a fire sprinkler monitoring system (I spoke to Ron on this)

Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by General
BLD18-04270 FIRE-Final Inspection2/19/20192/20/20192/20/2019 8:17:19 AMAPASS
Extinguisher and e light placement verified and passed. One door in Game room hall has locking hardware creating a potential man trap. Contractor will change to normal handset and show building inspector. Life safety passed.

Brian Phone #: ###-####
BLD19-00453 FIRE-Final Inspection2/19/20192/20/20192/19/2019 11:31:29 AMAFAIL
Provide suite number, provide fire exitinguishers upstairs and down as discussed, provide ADA compliant hardware on the main exit (Need building conference to decide which is main exit)

Brady Phone #: ###-####
BLD19-00454 FIRE-Final Inspection2/19/20192/20/20192/19/2019 11:30:00 AMAFAIL
Provide sticker at main entry exit, provide suite number, provide verification that plan review needs revised floor plan.

Brady Phone #: ###-####