NAF18-00110
| INSP-Conference | 2/20/2019 | 2/20/2019 | 2/20/2019 3:10:31 PM | P | CANC |
|
|
Bruce would like to reschedule for morning at 7:30. Call prior to going Phone #: 2086065557 >> Inspection requested via mobile web by Bruce
|
FIR18-00946
| INSP-Final Inspection | 2/18/2019 | 2/20/2019 | 2/20/2019 2:28:46 PM | P | FAIL |
|
|
No actual testing performed. Plan mods are needed showing the actual fire alarm panel installed, a smoke detector is needed over the facp, provide verification whether hvac shutdown is needed or not, provide plan mods or make field changes to strobes that are overspaced, provide device map as per the review comments.
Nate Schneider is point of contact, please call roughly 15 minutes prior to arriving to site. ###-#### Phone #: ###-#### Inspection requested via web by jason petty
|
FIR18-00139
| INSP-Final Inspection | 2/19/2019 | 2/20/2019 | 2/20/2019 2:00:25 PM | P | CANC |
|
|
Not ready for a final yet. Missing ceiling tile and the project related fire alarm was not ready. Mike Phone #: ###-####
|
FIR18-00926
| INSP-Sprinkler Rough-in | 2/19/2019 | 2/20/2019 | 2/20/2019 1:45:02 PM | P | CANC |
|
|
Please call before heading out, thank you! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
BLD18-04569
| FIRE-Final Inspection | 2/19/2019 | 2/20/2019 | 2/20/2019 10:40:20 AM | P | PASS |
|
|
Life safety passed
Randy Phone #: ###-####
|
FIR18-00940
| INSP-Final Inspection | 2/19/2019 | 2/20/2019 | 2/20/2019 10:14:13 AM | A | FAIL |
|
|
Need the strobe in the restroom removed and as-builts provided.
Inspection needs to be done around 7:30am Phone #: ###-#### Inspection requested via web by Rafe Barrett
|
NAF18-00138
| INSP-Final | 2/19/2019 | 2/20/2019 | 2/20/2019 10:13:36 AM | A | FAIL |
|
|
Provide indicators on the two new doors, provide sticker on the two new doors, repair rear exit door exit sign, provide verification of need of sprinkler protection at bottom of stairs in front of new tenant door. May need a fire sprinkler monitoring system (I spoke to Ron on this)
Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by General
|
BLD18-04270
| FIRE-Final Inspection | 2/19/2019 | 2/20/2019 | 2/20/2019 8:17:19 AM | A | PASS |
|
|
Extinguisher and e light placement verified and passed. One door in Game room hall has locking hardware creating a potential man trap. Contractor will change to normal handset and show building inspector. Life safety passed.
Brian Phone #: ###-####
|
BLD19-00453
| FIRE-Final Inspection | 2/19/2019 | 2/20/2019 | 2/19/2019 11:31:29 AM | A | FAIL |
|
|
Provide suite number, provide fire exitinguishers upstairs and down as discussed, provide ADA compliant hardware on the main exit (Need building conference to decide which is main exit)
Brady Phone #: ###-####
|
BLD19-00454
| FIRE-Final Inspection | 2/19/2019 | 2/20/2019 | 2/19/2019 11:30:00 AM | A | FAIL |
|
|
Provide sticker at main entry exit, provide suite number, provide verification that plan review needs revised floor plan.
Brady Phone #: ###-####
|