Inspections for the day of: Monday, February 24, 2020.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03898 FIRE-Final Inspection2/24/20202/24/20202/24/2020 3:18:22 PMPFAIL
Life safety will be ok to pass when the project related fire alarm permit is finaled.

Phone #: ###-#### Inspection requested via web by Nate Carriveau
FIR19-00883 INSP-Final Inspection2/24/20202/24/20202/24/2020 1:13:50 PMPFAIL
Not all of the strobes have been modified to meet the minimum spacing requirements of NFPA 72. There are strobes on the exterior balcony that are not shown on the plans. They will need to be shown if they are powered from the new NAC panel.


Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten