Inspections for the day of: Wednesday, February 26, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-03924 FIRE-Final Inspection2/26/20202/26/20202/26/2020 2:44:09 PMPFAIL
All items except the exterior exit door, as addressed on the previous inspection, have been corrected.. This door is shown as an egress door by the architect with the travel distance calculation. Door shall be provided with code compliant single action hardware and not exceed pull effort as per Chapter 10 of the IFC.

Site Contact Will Be Stephanie Day Phone #: ###-#### Inspection requested via web by Kristian Allison
BLD20-00195 FIRE-Final Inspection2/26/20202/26/20202/26/2020 2:12:59 PMPFAIL
No spection performed since plans have not been resubmitted to show the additional storage area at the back of the store.

Jason Phone #: ###-####
FIR19-00792 INSP-Sprinkler Rough-in2/25/20202/26/20202/26/2020 1:14:17 PMACANC
The plan mods were not on site when I arrived for the inspection. Will need to be rescheduled.

Tanner Phone #: ###-####
FIR19-00770 INSP-Final Inspection2/25/20202/26/20202/26/2020 11:22:57 AMAFAIL
Possible plan mods are needed due to the length of the actual underground supply, two houses fed off a single 1" supply and a 5/8" water meter. Repair the outside alarm bell and provide signage as discussed.
Cole will be the contact. Please give him an hours notice to meet you there. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
NAF20-00004 INSP-Sprinkler Rough-in2/25/20202/26/20202/26/2020 10:58:02 AMAPASS
Plan mods are acceptable. Piping can be covered.

Please contact Rick Fry for time of inspection. Phone #: ###-#### Inspection requested via web by Daniel Buccino
BLD19-02844 FIRE-Final Inspection2/25/20202/26/20202/26/2020 8:17:49 AMAPASS
Life safety passed.

Steve Phone #: ###-####