Inspections for the day of: Monday, February 4, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-04246 FIRE-Final Inspection2/4/20192/4/20192/4/2019 3:12:01 PMPFAIL
Need the project related fire alarm permit finaled, need door hardware installed, need fire extinguishers. Exit lights/emergency lights did function.

Tony Phone #: ###-####
FIR18-00965 INSP-Final Inspection2/4/20192/4/20192/4/2019 3:07:58 PMPPASS
permit finaled

Tony Phone #: ###-####
FIR17-00626 INSP-Final Inspection2/4/20192/4/20192/4/2019 1:42:19 PMPPART
Todays inspection was to verify that the fiber optic interconnection is functional which it was.

ARFF added to all devices descriptions going to the main panel. Phone #: ###-#### Inspection requested via web by Gary Gambino
NAF18-00086 INSP-Sprinkler Rough-in2/4/20192/4/20192/4/2019 1:40:06 PMPPASS
The pendant head on the third floor has been moved and is passed. Piping can not be covered until a tenting inspection has been passed.

Contact Andrew Larson ###-#### 0 Min Prior to RTC Insp start please for Lot A5.

Thank YOU
Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00600 INSP-Final Inspection2/1/20192/4/20192/4/2019 1:37:49 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Don Kartchner Inspection cancelled from web by: Don Kartchner
NAF18-00128 INSP-Sprinkler Rough-in2/4/20192/4/20192/4/2019 12:30:52 PMPPASS
The remaining sprinkler piping is ok for cover.

Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John Venche
NAF18-00086 INSP-Sprinkler Rough-in2/1/20192/4/20192/4/2019 10:44:13 AMAPART
See the city approved plans for the appartment that was inspected. The first and second floor piping can be covered but the third floor needs one pendant head adjusted to provide coverage and tenting approved prior to a cover approval. Andrew will reschedule a nother inspection for this afternoon to see tyhe head modified.


Contact Andrew Larson ###-#### 0 Min Prior to RTC Insp start please for Lot A5.

Thank YOU
Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00012 INSP-Final Inspection2/1/20192/4/20192/4/2019 9:18:31 AMAFAIL
Rough-in passed for the most part. There were no small documents, will need 200lb hydro, 24 hr air, trip test....ect. prior to a final.

please give half hour notice Phone #: ###-#### Inspection requested via web by jeremiah robison