Inspections for the day of: Wednesday, February 5, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-01949 FIRE-Final Inspection2/5/20202/5/20202/5/2020 3:56:21 PMPPASS
Life safety passed.

Doyle Phone #: ###-####
FIR19-00748 INSP-Sprinkler Rough-in2/4/20202/5/20202/5/2020 1:15:02 PMPPART
The previous corrections have been addressed. However new permits will be required for tenant work. No piping to be covered without additional permits.



Terry Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR19-00754 INSP-Final Inspection2/4/20202/5/20202/5/2020 12:47:17 PMAFAIL
Not ready for final due to the project related fire alarm permit. Previous corrections for sprinkler spacing have been corrected.

George Jess is the Contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-02037 FIRE-Final Inspection2/4/20202/5/20202/5/2020 11:19:17 AMACANC
No life safety sign off required for this permit.

Phone #: ###-#### Inspection requested via web by Zach Carter
FIR18-00188 INSP-Alarm Testing2/4/20202/5/20202/5/2020 10:55:40 AMAFAIL
No testing performed. The smoke detectors need to be relocated as discussed due to the concrete T construction causing obstructions to the smoke detectors. Spacing and function of the detectors to meet NFPA 72 21.3

Elevator Recall Final Phone #: ###-#### Inspection requested via web by Fire Scheduler
FIR20-00032 INSP-Final Inspection2/4/20202/5/20202/5/2020 9:08:56 AMAFAIL
Left message I was on the way. Arrived tried calling again but made no contact. No inspection perfromed.

Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
BLD20-00195 FIRE-Final Inspection1/30/20202/5/20202/5/2020 8:58:00 AMAFAIL
Resubmitt plans showing the large storage area at the back of the store and meet any additional requirements for exiting from this area. Provide emergency lighting in areas as discussed.

Jason Phone #: ###-####
FIR20-00005 INSP-Final Inspection1/31/20202/5/20202/5/2020 8:52:35 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Jason Heath