FIR11-00563
| INSP-Sprinkler Rough-in | 2/8/2012 | 2/8/2012 | 2/8/2012 3:19:26 PM | P | PART |
|
|
The pendant head on the third floor has been relocated but the fourth floor tenting and the deflection of the piping has not been addressed.
|
FIR09-00510
| FIR-Aging Inspection | 2/8/2012 | 2/8/2012 | 2/8/2012 2:57:26 PM | | NR |
|
|
Per matt casey issues are being worked out with the owner.
|
FIR11-00671
| INSP-Sprinkler Rough-in/Hydro | 2/7/2012 | 2/8/2012 | 2/8/2012 2:55:59 PM | P | PASS |
|
|
Hydro test passed.
|
BLD11-02578
| FIRE-Conference | 2/8/2012 | 2/8/2012 | 2/8/2012 2:55:20 PM | P | DONE |
|
|
I went over life safety requirements and inspection scheduling with the builder and Kevin Stees of Natural Foods.
|
BLD12-00190
| FIRE-Final Inspection | 2/8/2012 | 2/8/2012 | 2/8/2012 2:46:33 PM | P | PASS |
|
|
life safety passed. Owner to remove inoperative exit sign and dead bolt located at the top of the inactive leaf at the main exit
|
FIR12-00008
| INSP-Sprinkler Rough-in | 2/8/2012 | 2/8/2012 | 2/8/2012 2:00:06 PM | P | PASS |
|
|
The piping over the sales floor is ok to cover
|
FIR11-00527
| INSP-Sprinkler Rough-in | 2/7/2012 | 2/8/2012 | 2/8/2012 1:10:28 PM | A | PASS |
|
|
Sprinkler piping can be covered.
|
FIR11-00563
| INSP-Sprinkler Rough-in/Hydro | 2/8/2012 | 2/8/2012 | 2/8/2012 8:52:34 AM | A | FAIL |
|
|
Could not make contact with the fitter/contractor either by phone or in person. Wander all four floors. No inspection was performed. I did conference with the fire alarm vendor.
|
BLD11-02864
| FIRE-Final Inspection | 2/7/2012 | 2/8/2012 | 2/8/2012 8:24:36 AM | A | PASS |
|
|
life safety passed
|