Inspections for the day of: Tuesday, March 13, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00136 INSP-Final Inspection3/13/20183/13/20183/13/2018 2:19:17 PMPPASS
Permit finaled
BLD17-01088 FIRE-Final Inspection3/12/20183/13/20183/13/2018 1:37:21 PMAPART
Life safety in new addition passed. Passage 115 was not complete yet.

Charles Phone #: ###-####
FIR17-00596 INSP-Sprinkler Rough-in3/12/20183/13/20183/13/2018 1:30:05 PMAFAIL
No city approved drawings on site. No inspection performed. I also noted missing fire proofing.
BLD17-00058 FIRE-Final Inspection3/12/20183/13/20183/13/2018 1:23:20 PMAFAIL
Provide sign off from Boise FIre Dept, repair exit sign at west end of corridor, repair exit discharge light at west main exit, provide testing of communication, emergency stops and duct smoke detectors, remove dead bolt on the beer cooler, provide address numbers facing Cole Rd.

Phone #: ###-#### Inspection requested via web by Roger Graves
BLD18-00742 FIRE-Final Inspection3/9/20183/13/20183/13/2018 11:29:59 AMAFAIL
Provide a mounted/tagged fire extinguisher as discussed.

Christine Phone #: ###-####
BLD16-04077 FIRE-Final Inspection3/12/20183/13/20183/13/2018 11:01:04 AMAFAIL
Need the project related fire alarm and fire sprinkler permits finaled, Need city approved plans and small documents. No testing was performed.


Please coordinate with sprinkler and alarm.
Thanks Phone #: ###-#### Inspection requested via web by Chris Palmer
FIR17-00574 INSP-Final Inspection3/12/20183/13/20183/13/2018 11:00:11 AMAFAIL
Need dedicated circuit for the dialer, need plan mod for the dialer that is being used, need the modified candella for the Womens Restroom shown on the plan mods. No devices tested.


Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR17-00305 INSP-Final Inspection3/12/20183/13/20183/13/2018 10:59:01 AMAFAIL
Forward flush passed, need backflow tagged, need pad at the PIV. Could not test devices due to fire alarm permit issued.
BLD17-04659 FIRE-Final Inspection3/12/20183/13/20183/13/2018 9:43:28 AMAPASS
Life safety passed


early morning please - George Phone #: ###-####