FIR18-00136
| INSP-Final Inspection | 3/13/2018 | 3/13/2018 | 3/13/2018 2:19:17 PM | P | PASS |
|
|
Permit finaled
|
BLD17-01088
| FIRE-Final Inspection | 3/12/2018 | 3/13/2018 | 3/13/2018 1:37:21 PM | A | PART |
|
|
Life safety in new addition passed. Passage 115 was not complete yet.
Charles Phone #: ###-####
|
FIR17-00596
| INSP-Sprinkler Rough-in | 3/12/2018 | 3/13/2018 | 3/13/2018 1:30:05 PM | A | FAIL |
|
|
No city approved drawings on site. No inspection performed. I also noted missing fire proofing.
|
BLD17-00058
| FIRE-Final Inspection | 3/12/2018 | 3/13/2018 | 3/13/2018 1:23:20 PM | A | FAIL |
|
|
Provide sign off from Boise FIre Dept, repair exit sign at west end of corridor, repair exit discharge light at west main exit, provide testing of communication, emergency stops and duct smoke detectors, remove dead bolt on the beer cooler, provide address numbers facing Cole Rd.
Phone #: ###-#### Inspection requested via web by Roger Graves
|
BLD18-00742
| FIRE-Final Inspection | 3/9/2018 | 3/13/2018 | 3/13/2018 11:29:59 AM | A | FAIL |
|
|
Provide a mounted/tagged fire extinguisher as discussed.
Christine Phone #: ###-####
|
BLD16-04077
| FIRE-Final Inspection | 3/12/2018 | 3/13/2018 | 3/13/2018 11:01:04 AM | A | FAIL |
|
|
Need the project related fire alarm and fire sprinkler permits finaled, Need city approved plans and small documents. No testing was performed.
Please coordinate with sprinkler and alarm. Thanks Phone #: ###-#### Inspection requested via web by Chris Palmer
|
FIR17-00574
| INSP-Final Inspection | 3/12/2018 | 3/13/2018 | 3/13/2018 11:00:11 AM | A | FAIL |
|
|
Need dedicated circuit for the dialer, need plan mod for the dialer that is being used, need the modified candella for the Womens Restroom shown on the plan mods. No devices tested.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR17-00305
| INSP-Final Inspection | 3/12/2018 | 3/13/2018 | 3/13/2018 10:59:01 AM | A | FAIL |
|
|
Forward flush passed, need backflow tagged, need pad at the PIV. Could not test devices due to fire alarm permit issued.
|
BLD17-04659
| FIRE-Final Inspection | 3/12/2018 | 3/13/2018 | 3/13/2018 9:43:28 AM | A | PASS |
|
|
Life safety passed
early morning please - George Phone #: ###-####
|