Inspections for the day of: Thursday, March 15, 2018.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-00742 FIRE-Final Inspection3/14/20183/15/20183/16/2018 2:24:54 PMPPASS
Life safety passed

Please call ahead for access - Chris Phone #: ###-####
BLD17-00058 FIRE-Final Inspection3/13/20183/15/20183/15/2018 3:20:59 PMPPASS
Life safety passed.

Phone #: ###-#### Inspection requested via web by Roger Graves
BLD17-04218 FIRE-Conference3/15/20183/15/20183/15/2018 3:20:17 PMADONE
Justin and I discussed the issue of incorrect pipe sizing in this tenant space as shown on FIR17-00593. The main shown as 4" is actually 3". As per discussion with Scott Arellano the future FIR permit for the dry system (or separate submittal) will need to address this issue with calculations that verify the system does meet minimum code requirments.

Please call Justin 1/2-hour prior to site visit, thank you. Phone #: ###-#### Inspection requested via web by Justin Dauby
FIR17-00574 INSP-Final Inspection3/14/20183/15/20183/15/2018 1:48:34 PMPCANC
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Thursday, March 15, 2018.
BLD18-00277 FIRE-Final Inspection3/14/20183/15/20183/15/2018 1:24:37 PMAFAIL
Extend/modify the existing fire alarm systemto meet code and the original design intent of the fire alarm system FIR03-00750


Kenna Strickland (alt contact James Morson ###-####) Phone #: ###-####
BLD14-03139 FIRE-Final Inspection3/14/20183/15/20183/15/2018 12:51:08 PMAFAIL
Provide exit sign at the top of the interior room stairs as per plans, provide smoke detector actuation of the smoke dampers as per the IMC and provide testing of the duct smoke detector being utilized for hvac shutdown.

call when on way // Greg Phone #: ###-####
FIR16-00708 INSP-Final Inspection3/8/20183/15/20183/15/2018 12:49:29 PMACANC
Ray McQueen, inspecting technician Open building access Phone #: ###-#### Inspection requested via web by Rose Peterson
FIR17-00445 INSP-Supply line flush3/14/20183/15/20183/15/2018 10:05:28 AMAPASS
Underground flush passed
FIR17-00447 INSP-Supply line flush3/14/20183/15/20183/15/2018 10:04:58 AMAPASS
Underground flush passed
BLD18-00780 FIRE-Final Inspection3/13/20183/15/20183/15/2018 9:32:04 AMAFAIL
Need to provide testing of the smoke evac system, need to provide the two types of fire extinguishers, need to provide sprinkler canopies, need ADA hardware on the exit door, need permit and testing of the new hood suppression system

NIcholas Phone #: ###-####
BLD18-00781 FIRE-Final Inspection3/15/20183/15/20183/15/2018 9:30:32 AMAFAIL
Need to provide testing of the smoke evac system, need both fire extinguishers (K, ABC) provided as discussed. Taylor Brothers has tagged the three hood suppression systems.

NIcholas Phone #: ###-####
FIR18-00040 INSP-Final Inspection3/15/20183/15/20183/15/2018 8:55:49 AMPPASS
Permit finaled
FIR17-00541 INSP-Final Inspection3/14/20183/15/20183/15/2018 8:55:20 AMAPART
I verified the basement wet system tamper switches functioned/reported and I also verifed that the forward flush test passed

Rick Fry Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD17-04441 FIRE-Final Inspection3/14/20183/15/20183/15/2018 8:48:31 AMAPART
A temporary occupancy is given for the life safety until the remote annunciator for the fire alarm is installed and tested.


Mike Phone #: ###-####
FIR18-00053 INSP-Final Inspection3/14/20183/15/20183/15/2018 8:47:49 AMAPART
A remote annunciator is required for the duct smoke detector located above the ceiling in the Womens Locker Room as per NFPA 72 Chapter 7


Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR17-00596 INSP-Sprinkler Rough-in3/14/20183/15/20183/15/2018 7:27:16 AMAFAIL
Ceiling tile has not been installed in Passage 115


Contact Jon Olmstead ###-#### 30 min prior to RTC Start please Phone #: ###-#### Inspection requested via web by Teri Cruickshank