BLD18-00742
| FIRE-Final Inspection | 3/14/2018 | 3/15/2018 | 3/16/2018 2:24:54 PM | P | PASS |
|
|
Life safety passed
Please call ahead for access - Chris Phone #: ###-####
|
BLD17-00058
| FIRE-Final Inspection | 3/13/2018 | 3/15/2018 | 3/15/2018 3:20:59 PM | P | PASS |
|
|
Life safety passed.
Phone #: ###-#### Inspection requested via web by Roger Graves
|
BLD17-04218
| FIRE-Conference | 3/15/2018 | 3/15/2018 | 3/15/2018 3:20:17 PM | A | DONE |
|
|
Justin and I discussed the issue of incorrect pipe sizing in this tenant space as shown on FIR17-00593. The main shown as 4" is actually 3". As per discussion with Scott Arellano the future FIR permit for the dry system (or separate submittal) will need to address this issue with calculations that verify the system does meet minimum code requirments.
Please call Justin 1/2-hour prior to site visit, thank you. Phone #: ###-#### Inspection requested via web by Justin Dauby
|
FIR17-00574
| INSP-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 1:48:34 PM | P | CANC |
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Thursday, March 15, 2018.
|
BLD18-00277
| FIRE-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 1:24:37 PM | A | FAIL |
|
|
Extend/modify the existing fire alarm systemto meet code and the original design intent of the fire alarm system FIR03-00750
Kenna Strickland (alt contact James Morson ###-####) Phone #: ###-####
|
BLD14-03139
| FIRE-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 12:51:08 PM | A | FAIL |
|
|
Provide exit sign at the top of the interior room stairs as per plans, provide smoke detector actuation of the smoke dampers as per the IMC and provide testing of the duct smoke detector being utilized for hvac shutdown.
call when on way // Greg Phone #: ###-####
|
FIR16-00708
| INSP-Final Inspection | 3/8/2018 | 3/15/2018 | 3/15/2018 12:49:29 PM | A | CANC |
|
|
Ray McQueen, inspecting technician Open building access Phone #: ###-#### Inspection requested via web by Rose Peterson
|
FIR17-00445
| INSP-Supply line flush | 3/14/2018 | 3/15/2018 | 3/15/2018 10:05:28 AM | A | PASS |
|
|
Underground flush passed
|
FIR17-00447
| INSP-Supply line flush | 3/14/2018 | 3/15/2018 | 3/15/2018 10:04:58 AM | A | PASS |
|
|
Underground flush passed
|
BLD18-00780
| FIRE-Final Inspection | 3/13/2018 | 3/15/2018 | 3/15/2018 9:32:04 AM | A | FAIL |
|
|
Need to provide testing of the smoke evac system, need to provide the two types of fire extinguishers, need to provide sprinkler canopies, need ADA hardware on the exit door, need permit and testing of the new hood suppression system
NIcholas Phone #: ###-####
|
BLD18-00781
| FIRE-Final Inspection | 3/15/2018 | 3/15/2018 | 3/15/2018 9:30:32 AM | A | FAIL |
|
|
Need to provide testing of the smoke evac system, need both fire extinguishers (K, ABC) provided as discussed. Taylor Brothers has tagged the three hood suppression systems.
NIcholas Phone #: ###-####
|
FIR18-00040
| INSP-Final Inspection | 3/15/2018 | 3/15/2018 | 3/15/2018 8:55:49 AM | P | PASS |
|
|
Permit finaled
|
FIR17-00541
| INSP-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 8:55:20 AM | A | PART |
|
|
I verified the basement wet system tamper switches functioned/reported and I also verifed that the forward flush test passed
Rick Fry Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD17-04441
| FIRE-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 8:48:31 AM | A | PART |
|
|
A temporary occupancy is given for the life safety until the remote annunciator for the fire alarm is installed and tested.
Mike Phone #: ###-####
|
FIR18-00053
| INSP-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 8:47:49 AM | A | PART |
|
|
A remote annunciator is required for the duct smoke detector located above the ceiling in the Womens Locker Room as per NFPA 72 Chapter 7
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR17-00596
| INSP-Sprinkler Rough-in | 3/14/2018 | 3/15/2018 | 3/15/2018 7:27:16 AM | A | FAIL |
|
|
Ceiling tile has not been installed in Passage 115
Contact Jon Olmstead ###-#### 30 min prior to RTC Start please Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|