Inspections for the day of: Thursday, March 21, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00804 INSP-Sprinkler Rough-in/Hydro3/21/20193/21/20193/21/2019 2:53:42 PMPPART
24 hour air test started at 2:30 with 42psi on both guages for wings A and B.
BLD18-00943 FIRE-Final Inspection3/20/20193/21/20193/21/2019 2:26:45 PMPFAIL
Need the project related fire alarm, fire sprinkler and hood suppression permits addressed. Need occupant load signs as discussed and fire dept access signage for the parking lot on the north side of the new building. Neeed determination of ADA requirements for the manual pull for the hood suppression system.

Please try to come early afternoon working on other inspections.

thanks s Phone #: ###-#### Inspection requested via web by Russell Valline
BLD19-00269 FIRE-Final Inspection3/20/20193/21/20193/21/2019 2:14:18 PMPPASS
Life safety passed. Mark Phone #: ###-####
FIR19-00119 INSP-Final Inspection3/20/20193/21/20193/21/2019 2:07:35 PMPPASS
Permit finaled. Payton Phone #: ###-####
FIR19-00161 INSP-Sprinkler Rough-in3/21/20193/21/20193/21/2019 1:20:54 PMPPASS
Rough-in passed. Piping can be covered. Payton Phone #: ###-####
FIR18-00804 INSP-Sprinkler Rough-in/Hydro3/21/20193/21/20193/21/2019 12:25:46 PMPPASS
This Rough-in/hydro for wings A ; B was witnessed with no visible loss at the guages.
FIR18-00838 INSP-Final Inspection3/19/20193/21/20193/21/2019 12:01:57 PMACANC
The project related fire alarm permit was not ready for inspection. To be rescheduled. Brittany Phone #: ###-####
BLD19-00691 FIRE-Final Inspection3/20/20193/21/20193/21/2019 10:24:39 AMAPASS
Life safety passed. Sticker at door to be provided prior to a building inspection.

Phet Phone #: ###-####
FIR18-00675 INSP-Final Inspection3/20/20193/21/20193/21/2019 9:36:07 AMACANC
Fire alarm was not ready. To be rescheduled.
Robert Phone #: ###-####
FIR19-00080 INSP-Final Inspection3/20/20193/21/20193/21/2019 9:07:47 AMPFAIL
Not all of the plan package on site, drawings (facp, amp not same as drawings) no dialer shown, smoke over facp too low. No testing performed.


Partial Final for cafeteria and commons. Dirk is Contact. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD18-03023 FIRE-Final Inspection3/20/20193/21/20193/21/2019 7:39:50 AMACANC
No life safety, fire alarm or fire sprinkler sign off required per the permit details.

Call prior to going Phone #: 6027037603 >> Inspection requested via mobile web by Matthew Jimenez