FIR18-00804
| INSP-Sprinkler Rough-in/Hydro | 3/21/2019 | 3/21/2019 | 3/21/2019 2:53:42 PM | P | PART |
|
|
24 hour air test started at 2:30 with 42psi on both guages for wings A and B.
|
BLD18-00943
| FIRE-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 2:26:45 PM | P | FAIL |
|
|
Need the project related fire alarm, fire sprinkler and hood suppression permits addressed. Need occupant load signs as discussed and fire dept access signage for the parking lot on the north side of the new building. Neeed determination of ADA requirements for the manual pull for the hood suppression system.
Please try to come early afternoon working on other inspections.
thanks s Phone #: ###-#### Inspection requested via web by Russell Valline
|
BLD19-00269
| FIRE-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 2:14:18 PM | P | PASS |
|
|
Life safety passed. Mark Phone #: ###-####
|
FIR19-00119
| INSP-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 2:07:35 PM | P | PASS |
|
|
Permit finaled. Payton Phone #: ###-####
|
FIR19-00161
| INSP-Sprinkler Rough-in | 3/21/2019 | 3/21/2019 | 3/21/2019 1:20:54 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered. Payton Phone #: ###-####
|
FIR18-00804
| INSP-Sprinkler Rough-in/Hydro | 3/21/2019 | 3/21/2019 | 3/21/2019 12:25:46 PM | P | PASS |
|
|
This Rough-in/hydro for wings A ; B was witnessed with no visible loss at the guages.
|
FIR18-00838
| INSP-Final Inspection | 3/19/2019 | 3/21/2019 | 3/21/2019 12:01:57 PM | A | CANC |
|
|
The project related fire alarm permit was not ready for inspection. To be rescheduled. Brittany Phone #: ###-####
|
BLD19-00691
| FIRE-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 10:24:39 AM | A | PASS |
|
|
Life safety passed. Sticker at door to be provided prior to a building inspection.
Phet Phone #: ###-####
|
FIR18-00675
| INSP-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 9:36:07 AM | A | CANC |
|
|
Fire alarm was not ready. To be rescheduled. Robert Phone #: ###-####
|
FIR19-00080
| INSP-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 9:07:47 AM | P | FAIL |
|
|
Not all of the plan package on site, drawings (facp, amp not same as drawings) no dialer shown, smoke over facp too low. No testing performed.
Partial Final for cafeteria and commons. Dirk is Contact. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD18-03023
| FIRE-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 7:39:50 AM | A | CANC |
|
|
No life safety, fire alarm or fire sprinkler sign off required per the permit details.
Call prior to going Phone #: 6027037603 >> Inspection requested via mobile web by Matthew Jimenez
|