Inspections for the day of: Friday, March 27, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00158 INSP-Final Inspection3/27/20203/27/20203/27/2020 4:08:26 PMPFAIL
Dialer tested. Permit will need to be rescheduled for a final when test papers are received.

Phone #: ###-#### Inspection requested via web by Robert Gobler
FIR19-00319 INSP-Final Inspection3/26/20203/27/20203/27/2020 2:05:52 PMAPASS
Permit finaled.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
NAF20-00024 INSP-Sprinkler Rough-in3/27/20203/27/20203/27/2020 1:50:26 PMAPASS
The underground supply piping from the point of connection to with-in 5' of the building is ok for cover. Plans indicate 4" piping but 6" has been installed. Plans are to be resubmitted monday showing the actual installed pipe size as agreed.

Jeremiah - State Fire - ###-####
FIR20-00165 INSP-Sprinkler Rough-in3/26/20203/27/20203/27/2020 1:48:38 PMPPASS
See the city approved plans for four pendants/piping that are ok for cover at the new wall in lobby area. Please contact Troy Nelson for an inspection time. Phone #: ###-#### Inspection requested via web by Daniel Buccino
BLD18-03245 FIRE-Final Inspection3/26/20203/27/20203/27/2020 11:55:18 AMAPASS
Life safety passed. Boise Fire is ok with emergency radio.

josh Phone #: ###-####
BLD19-00101 FIRE-Final Inspection3/27/20203/27/20203/27/2020 11:12:51 AMPPASS
Life safety passed.

Jim Phone #: ###-####
BLD19-03981 FIRE-Final Inspection3/25/20203/27/20203/27/2020 11:10:15 AMAFAIL
Items on correction list have been addressed except for the duct smoke detectors. They will require a FIR permit as discussed. They will need to be tested for function. I noted that the incorrect remote annunciators have been installed and the duct smoke detectors are mounted on the supply side not the return side.. I let the store owner/employee take a picture of a cut sheet I had for the correct annunciator. I left a message for the contact listed below but he was not on site. I spoke to the tenant as stated.

Christian Phone #: ###-####
FIR20-00158 INSP-Final Inspection3/26/20203/27/20203/27/2020 8:19:05 AMAFAIL
No city approved plans on site.

Phone #: ###-#### Inspection requested via web by Robert Gobler