FIR20-00158
| INSP-Final Inspection | 3/27/2020 | 3/27/2020 | 3/27/2020 4:08:26 PM | P | FAIL |
|
|
Dialer tested. Permit will need to be rescheduled for a final when test papers are received.
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
FIR19-00319
| INSP-Final Inspection | 3/26/2020 | 3/27/2020 | 3/27/2020 2:05:52 PM | A | PASS |
|
|
Permit finaled.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
NAF20-00024
| INSP-Sprinkler Rough-in | 3/27/2020 | 3/27/2020 | 3/27/2020 1:50:26 PM | A | PASS |
|
|
The underground supply piping from the point of connection to with-in 5' of the building is ok for cover. Plans indicate 4" piping but 6" has been installed. Plans are to be resubmitted monday showing the actual installed pipe size as agreed.
Jeremiah - State Fire - ###-####
|
FIR20-00165
| INSP-Sprinkler Rough-in | 3/26/2020 | 3/27/2020 | 3/27/2020 1:48:38 PM | P | PASS |
|
|
See the city approved plans for four pendants/piping that are ok for cover at the new wall in lobby area. Please contact Troy Nelson for an inspection time. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
BLD18-03245
| FIRE-Final Inspection | 3/26/2020 | 3/27/2020 | 3/27/2020 11:55:18 AM | A | PASS |
|
|
Life safety passed. Boise Fire is ok with emergency radio.
josh Phone #: ###-####
|
BLD19-00101
| FIRE-Final Inspection | 3/27/2020 | 3/27/2020 | 3/27/2020 11:12:51 AM | P | PASS |
|
|
Life safety passed.
Jim Phone #: ###-####
|
BLD19-03981
| FIRE-Final Inspection | 3/25/2020 | 3/27/2020 | 3/27/2020 11:10:15 AM | A | FAIL |
|
|
Items on correction list have been addressed except for the duct smoke detectors. They will require a FIR permit as discussed. They will need to be tested for function. I noted that the incorrect remote annunciators have been installed and the duct smoke detectors are mounted on the supply side not the return side.. I let the store owner/employee take a picture of a cut sheet I had for the correct annunciator. I left a message for the contact listed below but he was not on site. I spoke to the tenant as stated.
Christian Phone #: ###-####
|
FIR20-00158
| INSP-Final Inspection | 3/26/2020 | 3/27/2020 | 3/27/2020 8:19:05 AM | A | FAIL |
|
|
No city approved plans on site.
Phone #: ###-#### Inspection requested via web by Robert Gobler
|