Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00159 INSP-Sprinkler Rough-in/Hydro3/29/20193/29/20193/29/2019 3:02:14 PMPPASS
The overhead hydro test for the south system passed.


Please Cordinate with Troy Nelson Phone #: ###-#### Inspection requested via web by Christophe Wilson
FIR18-00701 INSP-Sprinkler Rough-in3/29/20193/29/20193/29/2019 2:54:48 PMPPASS
See the city approved plans for piping above hardlids that can be covered.

Mike Phone #: ###-####
FIR18-00964 INSP-Sprinkler Rough-in3/28/20193/29/20193/29/2019 2:52:40 PMAPASS
Rough-in passed for system #2 and #6. Revised earthquake calculations are required for the 6" main. Piping in these areas are ok for cover. Piping near the new fire pump has not been installed.

Cordinate Inpsection with Lonnie Greenfield Phone #: ###-#### Inspection requested via web by Christophe Wilson
BLD19-00739 FIRE-Final Inspection3/28/20193/29/20193/29/2019 2:45:54 PMAFAIL
Repair or remove the exit sign, Provide single action lever type hardware on the rear exit, Provide fire sprinkler modifications or consult with the plan reviewer, Provide verification of a fire sprinkler monitoring system, Provide one 2A, 10BC fire extinguisher with current inspection tag, provide sticker at the main exit as discussed.

Jeff-please call to meet Phone #: ###-####
FIR19-00117 INSP-Sprinkler Rough-in/Hydro3/28/20193/29/20193/29/2019 1:36:11 PMPPASS
Overhead hydro test passed

Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00138 INSP-Sprinkler Rough-in3/28/20193/29/20193/29/2019 1:35:45 PMPPASS
Rough-in passed. Piping can not be covered until a tenting inspection has passed

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
NAF18-00124 INSP-Sprinkler Rough-in3/28/20193/29/20193/29/2019 12:35:08 PMPPASS
The large apartment on the very east end of the third floor is ok for soffit cover.

Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
FIR19-00161 INSP-Final Inspection3/29/20193/29/20193/29/2019 12:00:25 PMPPASS
permit finaled

John Phone #: ###-####
BLD19-00298 FIRE-Final Inspection3/28/20193/29/20193/29/2019 11:59:17 AMPPASS
Life safety passed

Phone #: ###-#### Inspection requested via web by Todd Kurns
NAF19-00021 INSP-Final3/27/20193/29/20193/29/2019 11:14:48 AMPFAIL
Need correct testing for the piping as discussed, need barrier between fryer and char broiler, need power under the hood to shut off as discussed.


Call prior to going Phone #: 2086157641 >> Inspection requested via mobile web by Richard
BLD19-00122 FIRE-Final Inspection3/28/20193/29/20193/29/2019 8:47:59 AMAPASS
Life safety passed. Per scope of work no occupancy under this permit. Fire alarm notification will need to be modified under an occupancuy permit. Robert Phone #: ###-####
FIR19-00209 INSP-Final Inspection3/28/20193/29/20193/29/2019 8:38:02 AMAPASS
Permit finaled

Tom Phone #: ###-####
BLD18-02471 FIRE-Final Inspection3/28/20193/29/20193/29/2019 8:25:20 AMAPASS
Life safety passed

Please contact Jim Hibbard 30 minutes prior to arrival Phone #: ###-#### Inspection requested via web by James Hibbard
BLD18-03918 FIRE-Final Inspection3/28/20193/29/20193/29/2019 12:00:00 AMACANC
Lloyd Phone #: ###-####
BLD18-03791 FIRE-Final Inspection3/28/20193/29/20193/29/2019 12:00:00 AMACANC
Lloyd Phone #: ###-####
NAF19-00021 INSP-Final3/27/20193/29/20193/27/2019 1:48:31 PMPCANC
Phone #: 2082584094 >> Inspection requested via mobile web by Britney Inspection cancelled via mobile web on Wednesday, March 27, 2019.
NAF19-00015 INSP-Final3/25/20193/29/20193/27/2019 9:53:34 AMACANC
Call prior to going Phone #: 2085658146 >> Inspection requested via mobile web by James Baker Inspection cancelled via mobile web on Wednesday, March 27, 2019.