Inspections for the day of: Thursday, March 7, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00088 INSP-Sprinkler Rough-in3/7/20193/7/20193/7/2019 12:21:03 PMPFAIL
Inspection was supposed to be a conference on the placement of pendant heads due to obstructions. Todd Phone #: ###-####
FIR19-00061 INSP-Sprinkler Rough-in3/7/20193/7/20193/7/2019 12:15:17 PMPFAIL
Revised plans are not on site and there is no access to the two first floor aparatments or to the riser room due to construction work blocking the doors

Nick Phone #: ###-####
FIR18-00435 INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019 11:23:21 AMAPASS
First floor concealed spaces have been filled with insulation. They can now be covered.
BLD19-00694 FIRE-Final Inspection3/6/20193/7/20193/7/2019 10:58:13 AMAPASS
life safety passed

Tonia Phone #: ###-####
NAF18-00085 INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019 10:19:59 AMAPART
The tenting inspection passed and piping can be covered. However I noticed a third floor closet appears to be used for mechanical. I spoke to Scott in Phoenix Fire office about this potential problem. Sprinkler protection may be required. He is going to follow up.

Andrew Larson Point of contact Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00083 INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019 10:19:39 AMAPART
The tenting inspection passed and piping can be covered. However I noticed a third floor closet appears to be used for mechanical. I spoke to Scott in Phoenix Fire office about this potential problem. Sprinkler protection may be required. He is going to follow up.

Andrew Larson Point of contact Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00084 INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019 10:19:20 AMAPART
The tenting inspection passed and piping can be covered. However I noticed a third floor closet appears to be used for mechanical. I spoke to Scott in Phoenix Fire office about this potential problem. Sprinkler protection may be required. He is going to follow up.

Andrew Larson Point of contact Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00629 INSP-Supply line flush3/5/20193/7/20193/7/2019 10:11:58 AMAPASS
The underground supply line flush passed.
NAF18-00124 INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019 10:10:40 AMAPASS
Rough-in passed for the third floor rooms to almost column line 3. See the general contractors record drawings for specific rooms.

Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
FIR18-00701 INSP-Sprinkler Rough-in/Hydro3/7/20193/7/20193/7/2019 8:54:39 AMAPASS
See the city approved plans for areas marked that I inspected today. A re-inspection for this area will be needed when the sprinkler drops have been cut in.

MIKE IS OUR FORMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt