Inspections for the day of: Friday, March 8, 2019.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00629 INSP-Sprinkler Rough-in/Hydro3/7/20193/8/20193/8/2019 1:42:21 PMPPASS
Under ground Hydro test witnessed with no visible loss at the guage.

Jim Danes Phone #: ###-#### Inspection requested via web by Connie Danes
FIR19-00103 INSP-Sprinkler Rough-in3/7/20193/8/20193/8/2019 12:55:10 PMAPASS
Rough-in passed. Tenting passed. Piping can be covered. Sprinkler protection for the second floor outside storage rooms may need to be modified. As-builts are needed showing the new sidewall coverage under the front entry gables.Rirers are not built yet.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00061 INSP-Sprinkler Rough-in3/7/20193/8/20193/8/2019 9:53:18 AMAPART
Rough-in passed. Tenting passed. Piping can be covered. Plan mods are needed again because instead of both risers being located on the first floor closet, the first floor is in the first floor closet but the second floor riser has been relocated to the second floor closet. Also heat to the wet piping in the closets has not been addressed. We also spoke about the need for a sprinkler riser monitoring system. Nick Phone #: ###-####
NAF18-00124 INSP-Sprinkler Rough-in3/7/20193/8/20193/8/2019 8:39:48 AMAPASS
The remaining third floor resident rooms are ok for cover at the deck except for the very end/northwest apartment that needs upright protection modified due to shearing that has been installed. I also noted missing upright protection in the northwest corridor and at the top of both stairs. Also both mechanical shafts, as per previous conversations, will need to be totally sheetrocked. I also noted that at the first floor east stairwell there is a exposed wood beam that is still exposed. Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken