FIR18-00136
| INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 3:04:54 PM | P | FAIL |
|
|
I went ahead and tested all the fire alarm devices per the scope of work and they tested/reported fine. For a final sign off I need plan mod showing the change of addresses and the AES dialer instead of the phone lines that are shown on the city approved plans. Mike L Phone #: ###-####
|
FIR17-00776
| INSP-Final Inspection | 3/7/2018 | 3/9/2018 | 3/9/2018 3:03:09 PM | P | PASS |
|
|
Permit finaled
|
BLD17-04005
| FIRE-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 3:00:49 PM | A | CANC |
|
|
Need the project related fire alarm permit inspected/finaled and access to the project.
Stoyanov Phone #: ###-####
|
FIR18-00097
| INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 2:57:04 PM | A | FAIL |
|
|
Arrived at the project at 7:45am and met contractor but we found that the police department was not there for access. I was unable to come back later in the day due to inspection load and no availability of the fire alarm contractor. No inspection performed.
Thank you! Jason Gordon Phone #: ###-#### Inspection requested via web by Neal Timmerman
|
FIR17-00460
| INSP-Sprinkler Rough-in/Hydro | 3/9/2018 | 3/9/2018 | 3/9/2018 2:50:48 PM | P | PASS |
|
|
Overhead hydro test passed
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00461
| INSP-Sprinkler Rough-in/Hydro | 3/9/2018 | 3/9/2018 | 3/9/2018 2:50:30 PM | P | PASS |
|
|
overhead hydro test passed
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00612
| INSP-Sprinkler Rough-in | 3/8/2018 | 3/9/2018 | 3/9/2018 1:55:11 PM | P | PART |
|
|
The only additional canopy that can have the piping covered in the west most/end of system . This canopy is in the walkway between the buildings. The other areas have issues with missing upright coverage and pendants and uprights not being installed as per plan.
Todd Ketterling is the contact for this inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR17-00499
| INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 1:26:49 PM | A | PASS |
|
|
permit finaled
Rick Phone #: ###-####
|
FIR17-00489
| INSP-Sprinkler Rough-in/Hydro | 3/9/2018 | 3/9/2018 | 3/9/2018 12:47:49 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
FIR17-00366
| INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 11:35:01 AM | A | FAIL |
|
|
The double doors did not release from the mag/hold opens upon alarm and a new single door that is "Delayed Egress Lock" was not connected to the fire alarm system for release as required by IFC 1008.1.9.7
|
FIR17-00576
| INSP-Sprinkler Rough-in/Hydro | 3/8/2018 | 3/9/2018 | 3/9/2018 10:38:12 AM | A | PASS |
|
|
The overhead hydro for the remaining piping passed.
Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00122
| INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 10:37:10 AM | A | FAIL |
|
|
Audio portion of the alarm was a solid tone not the required temporal. The new smoke detector did function correctly
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A
|
BLD17-02500
| FIRE-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 9:39:33 AM | A | FAIL |
|
|
No city approved plans or small documents on site. No inspection performed.
Julio Phone #: ###-####
|
FIR18-00181
| INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 8:56:10 AM | A | FAIL |
|
|
The work installed is ok but I"m noting that there is a lack of coverage in the "Mop Sink" area inside of the Break Room and the plans specify quick responce heads are being used but stardard heads are installed.
Please call Clarence thank you!
Happy Friday Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR18-00164
| INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 8:17:26 AM | A | PASS |
|
|
Permit finaled.
Phone #: ###-#### Inspection requested via web by Bruce Sullivan
|
FIR17-00694
| INSP-Supply line flush | 3/8/2018 | 3/9/2018 | 3/9/2018 8:04:13 AM | P | CANC |
|
|
Jordan is the contact for this flush. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR18-00114
| INSP-Alarm Testing | 3/8/2018 | 3/9/2018 | 3/9/2018 7:47:26 AM | A | PASS |
|
|
Partial inspection. See the city approved plans for specific area inspected and passed.
|