FIR20-00078
| INSP-Conference | 4/1/2020 | 4/2/2020 | 4/2/2020 3:11:59 PM | P | DONE |
|
|
Plan mods are needed showing the actual scope of work. Since this a panel replacement the entire system is required to meet current code. Notification devices are mounted too low and are missing in required locations. No actual testing was performed.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
FIR19-00815
| INSP-Sprinkler Rough-in | 4/1/2020 | 4/2/2020 | 4/2/2020 3:09:57 PM | P | FAIL |
|
|
Provide plan mods indicating the actual pipe routing. Repair tenting. It appears the FDC needs to be relocated to the street side of the building. It is currently on the west side in the yard/land scaping.
Call James before heading out, rough and tenting inspection. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD20-00651
| FIRE-Final Inspection | 3/24/2020 | 4/2/2020 | 4/2/2020 3:08:07 PM | P | PASS |
|
|
Life safety passed.
Jon Phone #: ###-####
|
FIR20-00186
| INSP-Sprinkler Rough-in | 4/1/2020 | 4/2/2020 | 4/2/2020 9:32:51 AM | A | CANC |
|
|
Tried to coordinate twice but it was not to be. Will need to be rescheduled.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
BLD20-01108
| FIRE-Final Inspection | 4/1/2020 | 4/2/2020 | 4/2/2020 9:32:15 AM | P | FAIL |
|
|
Provide notification in the Conference room as discussed. Other life saftey items are ok.
Rachel Phone #: ###-####
|
FIR20-00074
| INSP-Sprinkler Rough-in | 4/1/2020 | 4/2/2020 | 4/2/2020 9:31:02 AM | A | PASS |
|
|
See the city approved plans for locations marked "ok" where piping is ok to cover.
Please call Jon with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|