Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-01549 FIRE-Conference4/23/20194/23/20194/23/2019 2:47:06 PMPDONE
Renee and I discussed the location for the building address and agreed for it to be placed on the east side of the hose tower.
FIR19-00244 INSP-Final Inspection4/22/20194/23/20194/23/2019 2:00:19 PMPPASS
permit finaled

Phone #: ###-#### Inspection requested via web by David Ozmer
BLD19-00515 FIRE-Final Inspection4/23/20194/23/20194/23/2019 1:19:58 PMPPART
The life safety for the Restrooms is passed. I noted that sprinkler modifications will be required in the area the Factory expanded into. The sprinkler pendants were installed for light hazard but now need to meet ordinary hazard.

Please call 30 mins a head of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
FIR18-00918 INSP-Sprinkler Rough-in/Hydro4/22/20194/23/20194/23/2019 1:15:49 PMPPART
The general rough-in is ok except the Coin upright heads over the restrooms are installed too low as per the data sheet. Will need to restart the hydro due to the need to modify the pipe and heads.

POC is Raul Munoz Phone #: ###-#### Inspection requested via web by Chris Green
BLD19-00849 FIRE-Final Inspection4/22/20194/23/20194/23/2019 12:09:05 PMPPASS
Switch the suite numbers for 150 and 175 as shown on plans and provide single action hardware on the restroom doors as discussed prior to a building inspection.

please give 30 mins prior- Tom Phone #: ###-####
FIR19-00156 INSP-Sprinkler Rough-in/Hydro4/22/20194/23/20194/23/2019 10:17:06 AMAPASS
The overhead hydro was witnessed with no pressure loss.

Contact Tyler Loomis ###-#### 30 min prior to Hydro Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-00776 FIRE-Final Inspection4/22/20194/23/20194/23/2019 8:46:10 AMAFAIL
Life safety will be ok to pass after a fire alarm permit is pulled and finaled for the required modifications.

Able Phone #: ###-####
FIR17-00603 INSP-Final Inspection4/22/20194/23/20194/23/2019 8:39:45 AMAPART
Sprinkler work is complete for the five pendant heads in the north corridor.

Todd Ketterling is the contact. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-03430 FIRE-Final Inspection4/22/20194/23/20194/23/2019 8:38:13 AMAPASS
life safety passed.

Aaron Phone #: ###-####