Inspections for the day of: Friday, April 26, 2019.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00218 INSP-Sprinkler Rough-in/Hydro4/26/20194/26/20194/26/2019 1:27:15 PMPFAIL
Per the city approved plans the front area is considered an "M" occupancy and will need the pendant heads spaced for ordinary hazard not light hazard. Adam Phone #: ###-####
FIR18-00701 INSP-Sprinkler Rough-in4/26/20194/26/20194/26/2019 1:11:42 PMPPASS
See the city approved plans for areas marked where piping is ok for cover.

Mike Phone #: ###-####
BLD19-00515 FIRE-Final Inspection4/26/20194/26/20194/26/2019 1:07:40 PMPPART
Life safety passed for the Factory area. Fire sprinklers have been modified.

Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
FIR19-00295 INSP-Final Inspection4/26/20194/26/20194/26/2019 1:07:04 PMPPASS
Permit finaled

Please give us a call prior to heading out. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00295 INSP-Sprinkler Rough-in4/26/20194/26/20194/26/2019 1:06:41 PMPPASS
Rough-in passed.

Phone #: ###-#### Inspection requested via web by Sam Ball
NAF19-00042 INSP-Final4/23/20194/26/20194/26/2019 12:21:40 PMPCANC
It appears plan mods will be needed due to exhaust duct changes from the original design. Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
NAF19-00034 INSP-Conference4/25/20194/26/20194/26/2019 11:28:40 AMADONE
I went over life safety comments with the contractor

Call prior to going Phone #: 4056425898 >> Inspection requested via mobile web by Michael Houston
BLD18-02304 FIRE-Final Inspection4/25/20194/26/20194/26/2019 10:02:42 AMAFAIL
I need verification of all requirements listed under "Battery Storage" section of the fire code reveiw comments. Project superintendant stated these items were provided by Idaho Power.

Call half hour before // Jason Phone #: ###-####
BLD19-00515 FIRE-Final Inspection4/26/20194/26/20194/26/2019 9:40:56 AMPCANC
Please call 30 minutes ahead of time so I can meet you there. Phone #: ###-#### >> Inspection requested via web by Gerome Fries Inspection cancelled from web by: Gerome Fries
FIR19-00033 INSP-Supply line flush4/25/20194/26/20194/26/2019 9:32:59 AMAPASS
Underground flush witnessed

Nick Phone #: ###-####
FIR19-00060 INSP-Supply line flush4/25/20194/26/20194/26/2019 9:31:22 AMAPASS
Underground flush witnessed


Nick Phone #: ###-####
FIR19-00061 INSP-Supply line flush4/25/20194/26/20194/26/2019 9:29:13 AMAPASS
Underground flush witnessed

Nick Phone #: ###-####
FIR19-00059 INSP-Supply line flush4/25/20194/26/20194/26/2019 9:27:11 AMAPASS
Underground flush witnessed

Call ahead // Nick Phone #: ###-####
FIR19-00186 INSP-Sprinkler Rough-in4/25/20194/26/20194/26/2019 9:20:11 AMAPASS
Rough-in passed for remaining piping. Piping is ok for cover.
NAF19-00034 INSP-Sprinkler Rough-in/Hydro4/25/20194/26/20194/25/2019 2:53:28 PMACANC
Call prior to going Phone #: 4056425898 >> Inspection requested via mobile web by Michael Houston Inspection cancelled via mobile web on Thursday, April 25, 2019.
NAF19-00034 INSP-Conference4/25/20194/26/20194/25/2019 2:53:08 PMACANC
Call prior to going Phone #: 2056425898 >> Inspection requested via mobile web by Michael Houston Inspection cancelled via mobile web on Thursday, April 25, 2019.