FIR19-00033
| INSP-Sprinkler Rough-in | 4/9/2019 | 4/9/2019 | 4/9/2019 2:28:38 PM | P | PART |
|
|
Rough-in and tenting inspection passed. Plan modifications are needed showing the correct addrss (not building A), the additional pendant heads and pipe size changes prior to a final sign off. Also there were not review comments on site. These notes are required. No additional inspections on the remaining building will be given without the notes. If the notes require anything that has not been previously addressed it is the contractors responcibility to provide the changes at their cost. I let the general contractor know this as a condition for cover on this building. Piping is ok for cover.
Christen Phone #: ###-####
|
BLD19-00928
| FIRE-Final Inspection | 4/9/2019 | 4/9/2019 | 4/9/2019 2:16:58 PM | P | FAIL |
|
|
See the city approved floor plan for corrections noted in red which include resubmittals showing the actual wall layout and the stairs/mezzanine, blocked openings and doors, fire extinguisher issues, exterior door hardware issues, tire storage height issues, address number location......ect
Phabian Phone #: ###-####
|
NAF18-00124
| INSP-Sprinkler Rough-in | 4/8/2019 | 4/9/2019 | 4/9/2019 1:26:47 PM | P | PASS |
|
|
The piping above the soffits in the Community Room and Closet, on the first floor, is ok for cover.
Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
|
FIR19-00118
| INSP-Final Inspection | 4/8/2019 | 4/9/2019 | 4/9/2019 1:23:43 PM | P | PASS |
|
|
Permit finaled. Owners certificate provided for the Storage Room to remain light hazard and has been accepted by the Boise Fire.
Nathan Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD19-00230
| FIRE-Final Inspection | 4/9/2019 | 4/9/2019 | 4/9/2019 10:49:43 AM | P | PASS |
|
|
Life safety passed.
Troy. Lockbox code is 0912. Thx todd Phone #: ###-#### Inspection requested via web by Todd Kurns
|
NAF19-00029
| INSP-Final | 4/8/2019 | 4/9/2019 | 4/9/2019 10:48:48 AM | A | FAIL |
|
|
Need a permit/inspection for the hood suppression system, need appliance spacing under hood verified, need divider between fryer and four burner stove, need fire review comments, may need occupant load sign.
Call for access Phone #: 2085778794 >> Inspection requested via mobile web by Bob
|
FIR19-00033
| INSP-Sprinkler Rough-in | 4/8/2019 | 4/9/2019 | 4/9/2019 9:41:26 AM | A | FAIL |
|
|
The job site gate is locked so no inspection was performed.
Approved plans will be onsite in building A where the inspection will occur. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD18-03876
| FIRE-Final Inspection | 4/8/2019 | 4/9/2019 | 4/9/2019 9:19:59 AM | A | PASS |
|
|
life safety passed
call 10 mins ahead- Spencer Phone #: ###-####
|
BLD18-02795
| FIRE-Conference | 4/5/2019 | 4/9/2019 | 4/9/2019 9:18:11 AM | A | DONE |
|
|
Chad and I went over fire extinguisher placement, knox box location (deferred to Fire Dept), fire pump room requirements and sprinkler obstructions and small safety factor for the overhead system.
Chad Phone #: ###-####
|