Inspections for the day of: Friday, May 10, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00077 INSP-Sprinkler Rough-in5/9/20195/10/20195/10/2019 3:27:08 PMPCANC
Not all work was complete. To be rescheduled.Tom Phone #: ###-####
BLD17-04625 FIRE-Final Inspection5/9/20195/10/20195/10/2019 3:27:07 PMACANC
Not ready for life safety. Still need sprinkler final and paving has not been started yet for fire dept access. Bld C - FIRE / LIFE ; SAFETY re-inspection patched sprinkler holes Phone #: ###-#### Inspection requested via web by J.C. Murray
BLD18-03063 FIRE-Final Inspection5/9/20195/10/20195/10/2019 3:27:07 PMPFAIL
Mount the fire extinguishers as discussed, provide single action hardware as discussed and marked on the plans, provide missing exit sign, contact plan review about the second floor wall/door that is not shown on the plans. Provide sticker at the main exit. Phone #: ###-####
FIR18-00815 INSP-Final Inspection5/10/20195/10/20195/10/2019 1:49:56 PMPPASS
Permit finaled. Previous corrections addressed.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR17-00612 INSP-Final Inspection5/8/20195/10/20195/10/2019 1:39:22 PMAFAIL
The fire alarm contractor is not ready with the final fire alarm panel/srpinkler system. However the fire alarm work in the Day Care, Empty Tenant and Goodwill is complete. The correction required for the FDC to supply both the wet and dry systems has been completed.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00568 INSP-Sprinkler Rough-in5/9/20195/10/20195/10/2019 12:26:13 PMAPASS
The remaining underground supply piping is ok for cover.


THIS IS A UNDERGROUND COVER INSPECTION. TROY NELSON IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt
FIR19-00313 INSP-Final Inspection5/9/20195/10/20195/10/2019 10:18:46 AMACANC
Cancel per Chris Siewert, Technician Phone #: ###-#### Inspection requested via web by John Siewert
BLD19-00857 FIRE-Final Inspection5/6/20195/10/20195/10/2019 10:07:19 AMAFAIL
See city approved plans for locations of corrections that include needing annual inspection for all fire extinguishers and repairing exit signs and emergency lights that are non-functional. Sara Phone #: ###-####
BLD19-00926 FIRE-Final Inspection5/8/20195/10/20195/10/2019 8:55:23 AMAPASS
Life safety passed. Owner to remove deadbolt at the marked rear exit prior to a building inspection.

Dave Phone #: ###-####
BLD19-00860 FIRE-Final Inspection5/9/20195/10/20195/10/2019 8:43:35 AMAFAIL
Provide annual inspection for the fire extinguisher and provide exit sign/emergency light/exit discharge as per the approved plans.

John Phone #: ###-####
BLD19-00306 FIRE-Final Inspection5/8/20195/10/20195/10/2019 8:23:53 AMAPASS
Life safety passed
FIR19-00218 INSP-Final Inspection5/9/20195/10/20195/10/2019 8:23:31 AMAPASS
Permit finaled

Rick Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR19-00283 INSP-Final Inspection5/9/20195/10/20195/10/2019 7:22:37 AMAFAIL
The contractor and I could not gain access to the business. No testing performed. Nate Phone #: ###-####
FIR19-00067 INSP-Sprinkler Rough-in/Hydro5/8/20195/10/20195/10/2019 12:00:00 AMAPASS
**Underground hydro passed**MAS** Colton Cox is the contact. This inspection is for a hydro only. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus