Inspections for the day of: Thursday, May 16, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00349 INSP-Final Inspection5/15/20195/16/20195/16/2019 2:33:29 PMPPASS

Hood suppression system function for testing. Permit finaled


Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR19-00221 INSP-Sprinkler Rough-in5/16/20195/16/20195/16/2019 1:55:44 PMPPART
The existing underground supply piping is 4" instead of 6". Revised hydraulic calculations are required for the overhead system prior to a final sign off. The underground piping is ok for cover.


Please Contact Troy Nelson at ###-####, for time of inspection. This inspection is for underground rough -in. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR18-00787 INSP-Final Inspection5/15/20195/16/20195/16/2019 1:51:20 PMPFAIL
The wrong size of underground supply is still an issue. Need to flow water flow switch and test outside alarm bell.


Marcus Smith is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
NAF18-00124 INSP-Sprinkler Rough-in5/16/20195/16/20195/16/2019 1:47:27 PMPPASS
The remaing piping in the 2nd floor corridor is ok for cover. The remaining Resident rooms on the 3rd floor are ok for cover.

Call prior to going Phone #: 2082972020 >> Inspection requested via mobile web by Ken
NAF18-00124 INSP-Sprinkler Rough-in/Hydro5/16/20195/16/20195/16/2019 1:46:17 PMPCANC
Phone #: 2082979090 >> Inspection requested via mobile web by Teri Cruikshank
FIR18-00701 INSP-Sprinkler Rough-in/Hydro5/15/20195/16/20195/16/2019 10:16:13 AMAPASS
Rough-in complete for area B. All piping in area B can be covered. Overhead hydro test for area B witnessed with no pressure loss. Mike Phone #: ###-####
FIR18-00607 INSP-Final Inspection5/15/20195/16/20195/16/2019 10:15:09 AMAPASS
permit finaled

Mike Phone #: ###-####
FIR18-00787 INSP-Final Inspection5/15/20195/16/20195/15/2019 4:54:52 PMACANC
Marcus Smith is the contact. Thank you for the hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus