Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00293 INSP-Alarm Testing5/17/20165/17/20165/17/2016 2:13:41 PMPDONE
See the city approved plans for area/devices tested.
FIR13-00485 FIR-Aging Inspection5/17/20165/17/20165/17/2016 1:43:56 PM NR
Jeff is going to follow up on project status
BLD16-00451 FIRE-Final Inspection5/16/20165/17/20165/17/2016 12:43:19 PMPPASS
life safety passed. I dicussed with James that a racking permit may be required due to the storage racks that exceed 8'. They are light duty racks.
FIR16-00225 INSP-Final Inspection5/16/20165/17/20165/17/2016 12:42:09 PMAPASS
Permit finaled
FIR16-00253 INSP-Final Inspection5/16/20165/17/20165/17/2016 12:41:26 PMAFAIL
Can't cover yet since insulation is still hanging down blocking the upright sprinkler heads in two locations. Also Don and I discussed the overspaced pendants in the Dining area. It looks like he will need to add two pendants to provide the required coverage.
BLD16-00170 FIRE-Final Inspection5/17/20165/17/20165/17/2016 10:31:40 AMPPART
A temporary for life safety is being given with Scott's approval for a maximum of 30 days and only for the moving in of equipment. A final can be given when the project related fire alarm permit is finaled.
BLD15-04346 FIRE-Conference5/17/20165/17/20165/17/2016 9:03:04 AMPDONE
After dicussing lack of slope in the FIre Pump Room with Scott Arellano I spoke to the project superintendant about the floor slope issue and that there would be no final sign off on the life safety until the floor had been sloped as per previous discussions.
FIR16-00131 INSP-Conference5/17/20165/17/20165/17/2016 9:01:30 AMPDONE
After dicussing lack of slope in the FIre Pump Room with Scott Arellano I spoke to the project superintendant about the floor slope issue and that there would be no final sign off on the life safety until the floor had been sloped as per previous discussions.
FIR16-00131 INSP-Sprinkler Rough-in5/16/20165/17/20165/17/2016 8:20:20 AMAPASS
Four pendant heads as marked on the drawings are ok for cover. I noted that the Fire Pump Room floor has not been sloped except for maybe a 1'-0" circle around the floor drain which is positioned next to the north wall. I spoke to the job superintendant again and deferred him to Scott Arellano.
BLD15-04503 FIRE-Final Inspection5/16/20165/17/20165/17/2016 7:56:15 AMAPASS
life safety passed
FIR16-00245 INSP-Final Inspection5/16/20165/17/20165/17/2016 7:45:31 AMAPASS
Permit finaled