BLD18-00803
| FIRE-Final Inspection | 5/2/2019 | 5/2/2019 | 5/2/2019 2:31:38 PM | P | PASS |
|
|
Life safety passed.
Kevin Phone #: ###-#### Inspection requested via web by Kevin Antonucci
|
FIR18-00930
| INSP-Final Inspection | 5/2/2019 | 5/2/2019 | 5/2/2019 2:30:53 PM | P | PASS |
|
|
Permit finaled
|
FIR18-00525
| INSP-Sprinkler Rough-in | 5/1/2019 | 5/2/2019 | 5/2/2019 2:22:59 PM | P | PASS |
|
|
The piping above the hardlids in the first floor southwest restrooms and Corridor/Entry Lobby is ok to cover. Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00640
| INSP-Conference | 5/2/2019 | 5/2/2019 | 5/2/2019 2:05:40 PM | P | DONE |
|
|
I spoke to the building contractor about requirements for heat for the wet pipe system above the office.The contact is Cade. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00216
| INSP-Sprinkler Rough-in | 5/2/2019 | 5/2/2019 | 5/2/2019 2:04:22 PM | P | PASS |
|
|
Underground rough to cover is passed. Piping can be covered. Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
FIR18-00716
| INSP-Final Inspection | 5/1/2019 | 5/2/2019 | 5/2/2019 1:33:02 PM | P | FAIL |
|
|
need the interconnections with the fire alarm tested. Need ceiling at the ground floor north apartment repaired. All other areas the work appears complete.
Gerardo Arce is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00826
| INSP-Final Inspection | 5/1/2019 | 5/2/2019 | 5/2/2019 1:31:18 PM | P | FAIL |
|
|
Need the interconnection with the fire alarm system tested and balcony ceilings installed. Walk through of the apartments passed..
Gerardo Arce is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-01892
| FIRE-Final Inspection | 5/2/2019 | 5/2/2019 | 5/2/2019 12:36:57 PM | P | PASS |
|
|
life safety passed
Kevin Phone #: ###-####
|
BLD19-00277
| FIRE-Final Inspection | 5/2/2019 | 5/2/2019 | 5/2/2019 12:35:49 PM | P | PASS |
|
|
life safety passed
Kevin Phone #: ###-####
|
FIR19-00101
| INSP-Sprinkler Rough-in/Hydro | 5/1/2019 | 5/2/2019 | 5/2/2019 12:26:37 PM | P | FAIL |
|
|
Provide missing sprinkler head in bay window of master bedroom or provide exception, sprinkler heads are overspaced from the ceiling transition edge in the Kitchen area, provide sprinkler coverage under the second floor walkway as discussed, fix tenting as discussed. See the city approved plans for locations. Also the hydro test failed due to visible loss of pressure on the guage.
|
BLD17-00944
| FIRE-Final Inspection | 5/1/2019 | 5/2/2019 | 5/2/2019 11:25:17 AM | A | FAIL |
|
|
Repair the exit signs and provide the exit discharge light as per plans. Phone #: ###-#### Inspection requested via web by Bob Thornton
|
NAF19-00038
| INSP-Final | 5/1/2019 | 5/2/2019 | 5/2/2019 10:19:26 AM | A | FAIL |
|
|
Plan mods are needed for one hood due to changed nozzles numbers and one additional nozzle at the grill. All nozzles/piping needs braced and tightened so it does not spin in the fittings. Lights need to be repaired so shut off upon activation of the suppression system can be verified.
Call prior to going Phone #: 2086319935 >> Inspection requested via mobile web by Nate
|
FIR19-00077
| INSP-Sprinkler Rough-in | 5/1/2019 | 5/2/2019 | 5/2/2019 8:58:20 AM | A | PASS |
|
|
See the city approved plans for areas on the second floor where piping is ok for cover. Tom and I went over sprinkler coverage in/below the clouds.
Tom Phone #: ###-####
|
FIR17-00612
| INSP-Sprinkler Rough-in | 4/30/2019 | 5/2/2019 | 5/2/2019 8:18:36 AM | A | PASS |
|
|
24 hour air test witnessed with no visible loss on the guage.
|
FIR19-00258
| INSP-Sprinkler Rough-in | 5/1/2019 | 5/2/2019 | 5/2/2019 12:00:00 AM | P | PASS |
|
|
*** UG between main house and garage only. OK to cover. Trace wire to be added and left exposed on the interior to be inspected later. MAS***
Cover inspection for UG feed to garage. Please call Lonnie with time frame. Phone #: ###-#### >> Inspection requested via web by Jeff Packham
|
FIR18-00525
| INSP-Sprinkler Rough-in | 5/1/2019 | 5/2/2019 | 5/1/2019 3:54:44 PM | A | CANC |
|
|
Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|