Inspections for the day of: Monday, May 20, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF19-00056 INSP-Sprinkler Rough-in5/20/20195/20/20195/20/2019 3:16:54 PMPPART
Sprinkler spacing appears ok for State Fires scope of work but I noted painted heads, missing hangers. It also appears that the existing light fixtures/architectual features are blocking the pendant heads. This issues needs to be addressed now, which will require a plan modification, if it is with-in the building permit scope of work. If outside of the scope of work then the Boise Fire Dept will follow up for corrections.

Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00311 INSP-Final Inspection5/17/20195/20/20195/20/2019 3:10:06 PMPFAIL
Provide correct tamper switch, provide the smoke detector with-in 5' of the panel on the wall as discussed, clear the trouble signal on the FACP as discussed, provide knox key box, provide testing of devices.

Please call 30min before so I can meet on-site Phone #: ###-#### Inspection requested via web by Kyle Burgess
FIR19-00310 INSP-Final Inspection5/17/20195/20/20195/20/2019 3:09:39 PMPFAIL
Provide correct tamper switch, provide the smoke detector with-in 5' of the panel on the wall as discussed, clear the trouble signal on the FACP as discussed, provide knox key box, provide testing of devices. Phone #: ###-#### Inspection requested via web by Kyle Burgess
BLD19-00508 FIRE-Final Inspection5/20/20195/20/20195/20/2019 2:05:27 PMPFAIL
Need possible racking permit for the racks along the walls after discussion with the building inspector. Please contact the plan reviewer for clarification. All other life safety items appear ok.


Christian Phone #: 208-###-####
FIR19-00339 INSP-Sprinkler Rough-in5/20/20195/20/20195/20/2019 1:02:46 PMPPASS
Rough-in passed. Piping can be covered. Adam Phone #: ###-####
FIR19-00309 INSP-Sprinkler Rough-in5/17/20195/20/20195/20/2019 10:22:46 AMPPART
Tenting is not complete for the third floor. Rough-in for the first and third floors is complete except for acouple of tie-ins at the Breezeway. Riser room tenting is not complete.


Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
NAF19-00019 INSP-Supply line flush5/17/20195/20/20195/20/2019 10:16:46 AMAPASS
Underground supply line flush witnessed. Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
FIR19-00235 INSP-Final Inspection5/17/20195/20/20195/20/2019 9:34:51 AMAPASS
Permit finaled. Phone #: ###-#### Inspection requested via web by Mick Woodburn