Inspections for the day of: Wednesday, May 22, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00642 FIRE-Final Inspection5/22/20195/22/20195/22/2019 2:56:49 PMPFAIL
An exit sign needs to be added above the interior corridor exit as per the approved plans. I'm also noting that per the previous history of this building that notification devices have been required to be added into the tenant spaces as occupancy permits have been finaled. At this point this permit is not for occupancy therefore the fire alarm will not be an issue.

Sid Phone #: ###-####
FIR19-00339 INSP-Final Inspection5/22/20195/22/20195/22/2019 2:50:02 PMPPASS
Permit finaled
FIR18-00892 INSP-Sprinkler Rough-in/Hydro5/21/20195/22/20195/22/2019 2:35:55 PMPPART
Rough-in passed for the two story section of the project, this includes first and second floor. The opening made to install the piping can be repaired. Another rough-in inspection will be requried to verify that the existing blow-in insulation has been removed from below the new piping and adequate tenting has been provided over the new piping. This inspection needs to happen before the new blow-in insulation is installed. A partial hydro test was witnessed for this two story area and no loss on the second floor but a visible loss for the first floor. The single level area of the project is not ready for inspection yet.

Phone #: ###-#### Inspection requested via web by Connie Danes
NAF18-00124 INSP-Sprinkler Rough-in5/22/20195/22/20195/22/2019 2:10:20 PMPPART
The remaining piping in the third floor corridor is ok for cover. The rough-in for the Retail area is passed. It appears tha plan mods will be required for the changes in the Breeze Way and the Cover Parking area. These areas are having concealed space uprights being added and the pendants are on flex-heads.These areas can not be covered until approved by plan review and an inspection.

Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
FIR18-00913 INSP-Supply line flush5/22/20195/22/20195/22/2019 2:02:33 PMAPASS
.The underground supply line flush was witnessed and a verified flow of over 1500 gpm

Contact Andrew Larson ###-#### 30 min prior to Flush Insp start pelase

Thank YOU,
Teri Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00120 INSP-Sprinkler Rough-in/Hydro5/21/20195/22/20195/22/2019 2:02:33 PMAFAIL
Hydro test failed due to visible loss on the guage.
FIR19-00309 INSP-Sprinkler Rough-in5/21/20195/22/20195/22/2019 12:09:31 PMAFAIL
Tenting inspection failed. To be repaired as discussed in the breeze ways
FIR19-00045 INSP-Sprinkler Rough-in/Hydro5/22/20195/22/20195/22/2019 12:06:41 PMPFAIL
Hydro test failed due to visible loss on the guage.
FIR19-00045 INSP-Supply line flush5/21/20195/22/20195/22/2019 11:44:19 AMAPASS
The undergrond supply line flush was witnessed.
FIR19-00103 INSP-Sprinkler Rough-in/Hydro5/21/20195/22/20195/22/2019 11:40:10 AMAPASS
Overhead hydro tested witnessed with no visible loss on the guage.
BLD18-04088 FIRE-Final Inspection5/21/20195/22/20195/22/2019 11:28:21 AMAPASS
Life safety passed.

Please call Dan at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum