Inspections for the day of: Friday, May 3, 2019.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00218 INSP-Sprinkler Rough-in5/3/20195/3/20195/3/2019 3:19:54 PMPPASS
Rough-in passed. Piping can be covered.

Jon O Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR19-00101 INSP-Sprinkler Rough-in/Hydro5/3/20195/3/20195/3/2019 2:09:59 PMPPASS
Corrections made. Tenting passed. Piping can be covered.

As Built Plans approved. Call James to coordinate Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00231 INSP-Final Inspection5/2/20195/3/20195/3/2019 1:18:41 PMPPASS
Permit finaled

Please call clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR18-00267 INSP-Conference5/2/20195/3/20195/3/2019 12:57:39 PMADONE
We spoke about cordination of Vesda inspection and final sprinkler inspecton in regards to ceiling tile installation. Project walk, expectations for close out // Justin Phone #: ###-####
FIR18-00932 INSP-Final Inspection5/3/20195/3/20195/3/2019 11:45:57 AMPPASS
Permit finaled. Building permit has been issued.

Kirsten Phone #: ###-####
FIR19-00253 INSP-Sprinkler Rough-in/Hydro5/2/20195/3/20195/3/2019 11:43:23 AMAPASS
Rough-in passed. Piping can be covered.

Please call clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR19-00156 INSP-Final Inspection5/3/20195/3/20195/3/2019 10:55:20 AMPCANC
Contact Leroy Anderson ###-#### prior to Fire Final Insp start please... We would like to schedule this for 2 O''Clock PM if possible please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
FIR19-00253 INSP-Final Inspection5/2/20195/3/20195/3/2019 10:49:44 AMPCANC
Please call clarence Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
FIR19-00156 INSP-Sprinkler Rough-in5/2/20195/3/20195/3/2019 10:44:56 AMAFAIL
Not all work has been completed. Such as relocating uprights along the new walls and adding/relocating heads around the ceiling fans and in storage rooms. Missing canopies in the mens showers.

Leroy is the contact ###-#### Phone #: ###-#### Inspection requested via web by Scott Carter II
FIR19-00267 INSP-Sprinkler Rough-in5/3/20195/3/20195/3/2019 10:40:18 AMAFAIL
No city approved plans on site. No inspection was performed
FIR18-00882 INSP-Sprinkler Rough-in5/2/20195/3/20195/3/2019 9:37:01 AMAPASS
Rough-in passed and piping is ok for cover for both of the entry lobbys from the gym

Rick Phone #: ###-####
FIR19-00231 INSP-Sprinkler Rough-in/Hydro5/2/20195/3/20195/3/2019 9:07:09 AMAPASS
Please call clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR19-00215 INSP-Sprinkler Rough-in5/2/20195/3/20195/3/2019 8:46:14 AMAPASS
The rough-in passed for the remaining piping for the south half of the buiding. Tenting passed. All piping can be covered.
FIR18-00435 INSP-Sprinkler Rough-in5/2/20195/3/20195/3/2019 8:07:37 AMAPASS
The rough-in is for 2 heads in the main west entrance hard lid passed. Piping can be covered. The contact says this can take place anytime today (5/2) or tomorrow (5/3). Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00233 INSP-Sprinkler Rough-in5/3/20195/3/20195/3/2019 12:00:00 AMPPASS
*** OK to cover underground. No hydro or flush at this time.*MAS***
underground rough. Will call when ready. Phone #: ###-#### >> Inspection requested via web by Matthew Lewis
FIR19-00141 INSP-Sprinkler Rough-in5/3/20195/3/20195/3/2019 12:00:00 AMPPASS
***Rough inspection pass. No hydro.**MAS***
The space is in the basement east of the elevator plans are on supervisors desk. Phone #: ###-#### >> Inspection requested via web by Sam Ball