FIR19-00267
| INSP-Final Inspection | 5/6/2019 | 5/6/2019 | 5/6/2019 3:44:36 PM | P | CANC |
|
|
|
BLD17-04612
| FIRE-Final Inspection | 5/3/2019 | 5/6/2019 | 5/6/2019 3:39:19 PM | P | PASS |
|
|
Life safety passed. Contractor is going to provide an occupant load sign for the Conference room prior to a building inspection.
Jeff Phone #: ###-####
|
FIR19-00302
| INSP-Final Inspection | 5/3/2019 | 5/6/2019 | 5/6/2019 2:37:46 PM | P | PASS |
|
|
Permit finaled
Please call Jack at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR18-00918
| INSP-Final Inspection | 5/3/2019 | 5/6/2019 | 5/6/2019 2:37:46 PM | P | PASS |
|
|
Permit finaled
Contact name is Raul Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00060
| INSP-Sprinkler Rough-in | 5/6/2019 | 5/6/2019 | 5/6/2019 2:28:25 PM | P | PART |
|
|
Rough-in passed but piping can not be covered until a tenting inspection has passed.
Nick Phone #: ###-####
|
NAF19-00018
| INSP-Final | 5/6/2019 | 5/6/2019 | 5/6/2019 1:37:14 PM | P | DONE |
|
|
life safety passed
Call prior to going Phone #: 2086066055 >> Inspection requested via mobile web by Annie
|
FIR19-00059
| INSP-Sprinkler Rough-in | 5/6/2019 | 5/6/2019 | 5/6/2019 1:20:14 PM | P | PASS |
|
|
Rough-in passed. Tenting passed. Piping can be covered. The wet pipe in the exterior closets will need addressed as per previous conversations.
###-#### Nick
|
NAF18-00124
| INSP-Sprinkler Rough-in | 5/6/2019 | 5/6/2019 | 5/6/2019 1:18:37 PM | P | PASS |
|
|
Verified E.Q. bracing at first floor riser and giving ok to cover for east end of the third floor corridor.
Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
|
FIR19-00156
| INSP-Final Inspection | 5/3/2019 | 5/6/2019 | 5/6/2019 1:15:06 PM | A | PASS |
|
|
Permit finaled
|
BLD19-01464
| FIRE-Final Inspection | 5/3/2019 | 5/6/2019 | 5/6/2019 12:34:54 PM | A | CANC |
|
|
Wrong permit number scheduled. Brandi Phone #: ###-####
|
BLD18-03446
| FIRE-Final Inspection | 5/3/2019 | 5/6/2019 | 5/6/2019 11:18:37 AM | A | FAIL |
|
|
Provide the bollards for the fire hydrant protection as per the plans and provide corrected door hardware as per conversation.
Call to be badged in // Rick Phone #: ###-####
|
FIR18-00916
| INSP-Sprinkler Rough-in | 5/3/2019 | 5/6/2019 | 5/6/2019 11:17:44 AM | A | FAIL |
|
|
Todays inspection was for the first floor hardlids. Piping can not be covered because the approved plans show 1 1/4" starters but 1" has been installed. Also no branchline restraints have been installed. There were no small documents or notes on site. I appears the trapeze bracing attachment rods are too small.
Contact Andrew Larson ###-#### 30 Min Prior to RTC Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00156
| INSP-Sprinkler Rough-in | 5/3/2019 | 5/6/2019 | 5/6/2019 9:49:20 AM | A | PASS |
|
|
Rough-in passed. Corrections made. Permit can be finaled when alarm interconnections are verified.
|
FIR19-00267
| INSP-Sprinkler Rough-in | 5/3/2019 | 5/6/2019 | 5/6/2019 8:40:12 AM | A | PASS |
|
|
The sprinkler piping above the hardlids is ok for cover.
Contact Leroy Anderson ###-#### 30 min prior to RTC insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD18-04402
| FIRE-Final Inspection | 5/3/2019 | 5/6/2019 | 5/6/2019 7:13:24 AM | A | PASS |
|
|
life safety passed. Mike Phone #: ###-####
|
FIR19-00126
| INSP-Sprinkler Rough-in | 5/6/2019 | 5/6/2019 | 5/6/2019 12:00:00 AM | P | FAIL |
|
|
** Head needs to be added on other side of duct. If sheetrock doen't go all the way to the deck a head outside the chase on both sides of the duct would be acceptable.***MAS***
Contact Ken Orahood - ###-#### 30 min prior to RTC Insp start please
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank
|