Inspections for the day of: Monday, June 10, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00913 INSP-Conference6/10/20196/10/20196/10/2019 3:45:43 PMPDONE
I let Andrew know that if they need to repair the underground piping a new flush and hydro would be required.
FIR19-00145 INSP-Final Inspection6/8/20196/10/20196/10/2019 2:52:08 PMPFAIL
Need to test the flow switch, need to test the two duct smoke detectors, need as-builts.

Phone #: ###-#### Inspection requested via web by John Lopez
BLD19-00261 FIRE-Final Inspection6/10/20196/10/20196/10/2019 2:13:44 PMPFAIL
Jason and I went over life safety requirements to allow occupancy in part of the scope of work. Jason Phone #: ###-####
FIR19-00328 INSP-Sprinkler Rough-in6/7/20196/10/20196/10/2019 12:54:06 PMPPASS
3 heads in hardlids for bathrooms are ok for cover on the second floor.. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-00238 FIRE-Final Inspection6/7/20196/10/20196/10/2019 11:35:01 AMAPART
A temp for life safety is ok until the required NFPA Medical Gas Signage has been provided on the Medical Gas Room door.

Phone #: ###-#### Inspection requested via web by Drew Moorhouse
BLD19-00956 FIRE-Final Inspection6/7/20196/10/20196/10/2019 10:54:43 AMAPASS
Life safety passed

Chad Phone #: ###-####
FIR19-00303 INSP-Final Inspection6/10/20196/10/20196/10/2019 10:54:06 AMPPASS
Underground Finaled.

Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD19-00242 FIRE-Final Inspection6/6/20196/10/20196/10/2019 9:10:47 AMAFAIL
The only item ready for testing/inspection was the smoke evac system which functioned correctly.

David Phone #: ###-####