Inspections for the day of: Tuesday, June 18, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00221 INSP-Sprinkler Rough-in6/17/20196/18/20196/18/2019 2:25:24 PMPPASS
Rough-in passed for third floor north side apartment, all piping can be covered in this apartment. See city approved plans for notations.

tom Phone #: ###-####
BLD19-01444 FIRE-Final Inspection6/17/20196/18/20196/18/2019 2:13:07 PMAFAIL
Storage Room sprinkler heads are overspaced for Ordinary Hazard, add sprinkler coverage for new restroom, tag and mount the fire extinguisher, test the exit signs/emergency lights, provide annual inspection for the sprinkler system

Please Call Chad for access to building-he will meet on site. Phone #: ###-#### Inspection requested via web by Chad Aland
FIR18-00680 INSP-Final Inspection6/18/20196/18/20196/18/2019 1:05:33 PMPPASS
Permit finaled

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-00872 FIRE-Final Inspection6/18/20196/18/20196/18/2019 12:18:42 PMPFAIL
Provide sprinkler coverage for the massage room missing a head, repair the emergency light in the corridor and provide verification of annual inspection of the sprinkler system.

Call for access // John Phone #: ###-####
FIR19-00327 INSP-Sprinkler Rough-in6/17/20196/18/20196/18/2019 10:04:18 AMAFAIL
Plan needs to be mirror imaged, pipe routing and number of heads installed needs to match plans, will need to be tented prior to a cover inspection approval.

Colton Cox is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00698 INSP-Sprinkler Rough-in6/17/20196/18/20196/18/2019 9:48:36 AMAPASS
The underground supply line had a leak, was repaired and now can be re-covered.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00697 INSP-Sprinkler Rough-in6/17/20196/18/20196/18/2019 9:44:47 AMAPASS
The underground supply line had a leak, was repaired and now can be re-covered.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
NAF18-00148 INSP-Final6/17/20196/18/20196/18/2019 9:29:55 AMADONE
Life safety passed

Call prior to going Phone #: 2088615562 >> Inspection requested via mobile web by Ken
BLD18-01080 FIRE-Conference6/17/20196/18/20196/18/2019 8:31:19 AMADONE
We went over life safety requirements, need plans, need to relocate fire extinguisher, need to verify the smoke alarms ring back.

Charles Phone #: ###-####
FIR18-00957 INSP-Sprinkler Rough-in6/17/20196/18/20196/18/2019 8:06:46 AMAPASS
Todays inspection was for sprinkler system #2 in the "Show Room" area. Rough-in passed but plan mods will be needed to show all of the additional 90's in the branchlines and the ones in the mains. Pendants have not been installed. Mezzanine and Canopy piping has not been installed.

Phone #: ###-#### Inspection requested via web by Brad Bettencourt