BLD18-02125
| FIRE-Final Inspection | 6/18/2018 | 6/19/2018 | 6/19/2018 3:05:22 PM | P | FAIL |
|
|
Need to repair or remove the non-functional exit sign
call 10 mins ahead- Jennifer Phone #: ###-####
|
NAF18-00061
| INSP-Sprinkler Rough-in | 6/19/2018 | 6/19/2018 | 6/19/2018 2:56:06 PM | A | FAIL |
|
|
Todays inspection was for the west end, cpvc piping as marked on the plans. I noted that the pipe sizing does not match in the Resident room as marked on the plans, residential pendants have been installed in the Corridor, pendant heads are overspaced in the Corridor, there are many "shadowed" areas in the Resident Room Restrooms, 2 1/2" cpvc piping has been installed where steel piping is shown, piping is missing earthquake bracing. No tenting has been installed yet.
Call prior to going Phone #: 2088613011 >> Inspection requested via mobile web by Matt-overhead inspection
|
NAF18-00048
| INSP-Sprinkler Rough-in | 6/18/2018 | 6/19/2018 | 6/19/2018 2:51:27 PM | A | PASS |
|
|
The remaining underground piping is ok for cover.
|
FIR18-00411
| INSP-Sprinkler Rough-in | 6/18/2018 | 6/19/2018 | 6/19/2018 2:27:19 PM | P | CANC |
|
|
To be rescheduled for tomorrow morning.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00012
| INSP-Supply line flush | 6/18/2018 | 6/19/2018 | 6/19/2018 2:26:28 PM | P | PASS |
|
|
The supply line flush of the 4" passed. We did not flush the breeze way piping today.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
NAF18-00069
| INSP-Conference | 6/18/2018 | 6/19/2018 | 6/19/2018 11:23:59 AM | P | FAIL |
|
|
Provide approved plans and all small documents. Provide resubmittal showing the large storage room on the north side of building (contractor says it is not shown), provide fire extinguishers as discussed, provide correct address, remove all deadbolts and round door knobs on the exterior doors and provide single action hardware lever type, keyed hardware and sticker is ok at main exit. I need verification the existing sprinkler system could be demolished.
Call prior to going Phone #: 2088710075 >> Inspection requested via mobile web by Gary
|
FIR18-00411
| INSP-Supply line flush | 6/18/2018 | 6/19/2018 | 6/19/2018 10:24:21 AM | P | PASS |
|
|
The main underground supply line flush and the three breeze way supply flushes passed.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-00902
| FIRE-Final Inspection | 6/18/2018 | 6/19/2018 | 6/19/2018 10:23:14 AM | A | CANC |
|
|
Not ready per Chad Phone #: ###-####
|
FIR18-00219
| INSP-Sprinkler Rough-in | 6/18/2018 | 6/19/2018 | 6/19/2018 8:31:45 AM | A | FAIL |
|
|
Water curtain area piping not installed yet. No small documents on site. Plan modifications are needed to show the additional 90's in the sprinkler mains, branchlines and sprinkler drops of both remote areas. Earthquake bracing model/type installed is not the type used. Earthquake bracing missing or installed in wrong location. Bracing may be exceeding 7' in length. Retaining straps and branchline restraints are missing. The two dry sidewalls show on the plans have been deleted and two pendants installed in their place but are attached to a dry system with no return bends. This dry system piping is not shown on the approved plans. No piping can be covered. I did allow borders to be installed.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00327
| INSP-Sprinkler Rough-in/Hydro | 6/18/2018 | 6/19/2018 | 6/19/2018 7:54:47 AM | A | PART |
|
|
24 hour air test dry system started at 8:00am with 43psi on the guage.
|