FIR12-00518
| FIR-Aging Inspection | 6/27/2013 | 6/27/2013 | 6/28/2013 3:31:51 PM | | PASS |
|
|
permit finaled
|
FIR12-00561
| FIR-Aging Inspection | 6/27/2013 | 6/27/2013 | 6/28/2013 3:30:14 PM | | NR |
|
|
waiting on the outcome of fir13-00257
|
FIR12-00490
| FIR-Aging Inspection | 6/27/2013 | 6/27/2013 | 6/28/2013 12:12:56 PM | | DONE |
|
|
work is in progress
|
BLD13-01231
| FIRE-Final Inspection | 6/27/2013 | 6/27/2013 | 6/27/2013 3:40:41 PM | P | PASS |
|
|
life safety passed
|
FIR13-00218
| INSP-Sprinkler Rough-in | 6/26/2013 | 6/27/2013 | 6/27/2013 3:25:10 PM | A | PART |
|
|
I found some of the pendant sprinkler protection had been modified as per the last on site conference but several location the heads had not been modified to match plan so they remain out of code compliance. I found several areas with overspaced heads, which per the sprinkler fitter stated were outside of his scope of work. After speaking to Tim Frost on the soffits and cabinetry we are of the opion to meet NFPA 13 4.1 , that the sprinkler coverage is to be provided behind/extend to the wall behind the soffit. The cabinetry appears to be mobile. Tim spoke to Brad at TVFP about the issue. It also appears that a plan modification will be required since the wall and soffit and sprinkler head installation\layout does not match the city approved plans.
|
FIR13-00255
| INSP-Sprinkler Rough-in/Hydro | 6/27/2013 | 6/27/2013 | 6/27/2013 3:08:35 PM | P | PASS |
|
|
See the city approved plans for the two locations where sprinkler piping can be covered which includes dry storage and a short corridor.
|
BLD12-02063
| FIRE-Final Inspection | 6/27/2013 | 6/27/2013 | 6/27/2013 3:04:01 PM | P | FAIL |
|
|
Will be ok to final when the project related fire alarm permit is passed.
|
BLD13-01232
| FIRE-Final Inspection | 6/27/2013 | 6/27/2013 | 6/27/2013 2:34:46 PM | P | PASS |
|
|
Life safety passed
|
BLD13-01138
| FIRE-Final Inspection | 6/27/2013 | 6/27/2013 | 6/27/2013 2:33:40 PM | P | FAIL |
|
|
Repair the high exit sign on the east wall, remove or repair the exit sign on the west wall in the warehouse, provide racking permit for the racking that exceeds 8', relocate the exit sign at the main exit to be over the door, provide request to exit button and verification of tie in to the facp of the access controled egress doors, provide small documents and mount the fire extinguishers as discussed.
|
BLD12-00800
| FIRE-Final Inspection | 6/26/2013 | 6/27/2013 | 6/27/2013 12:51:30 PM | A | FAIL |
|
|
JULIO and I actually had a conference and discussed life safety requirements. I noted that only the main exit door is allowed to have keyed hardware where-as many of the interior doors are aluminum store front type with keyed hardware. We also discussed fire extinguisher plancement and the location of the address numbers.
|
FIR13-00257
| INSP-Alarm Testing | 6/26/2013 | 6/27/2013 | 6/27/2013 12:46:41 PM | A | CANC |
|
|
Steve did not want to test after 8:00am and the approved plans were not on site.
|