BLD16-00065
| FIRE-Final Inspection | 6/27/2016 | 6/27/2016 | 6/27/2016 2:06:33 PM | P | PASS |
|
|
Life safety passed. She is going to follow up with plan review for the missing exit sign. It is shown on the plans but based on the occupant load does not appear to be required.
|
BLD16-02067
| FIRE-Final Inspection | 6/27/2016 | 6/27/2016 | 6/27/2016 2:05:17 PM | P | PASS |
|
|
life safety passed
|
FIR16-00131
| INSP-Sprinkler Rough-in | 6/27/2016 | 6/27/2016 | 6/27/2016 12:45:43 PM | P | PASS |
|
|
Office area piping and pendants are complete. I noted one pendant head has been painted in the restroom accessible from the hanger. Heads in pump room not complete yet.
|
BLD16-02067
| FIRE-Final Inspection | 6/24/2016 | 6/27/2016 | 6/27/2016 8:48:10 AM | A | FAIL |
|
|
No city approved drawings on site. Contact is not answering phone as I left two messages.
|