Inspections for the day of: Monday, June 30, 2014.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00428 INSP-Final Inspection6/30/20146/30/20146/30/2014 3:36:09 PMPPASS
Permit finaled
FIR12-00698 INSP-Alarm Testing6/30/20146/30/20146/30/2014 3:24:23 PMPDONE
Additional area in the remodeled ER area passed. Need two smoke detectors relocated to the center line of the doors and with-in 5'
FIR14-00222 INSP-Supply line flush6/26/20146/30/20146/30/2014 3:23:06 PMPFAIL
Underground supply piping was not ready for inspection. Anthony and I discussed sprinkler protection in the concealed spaced.
FIR14-00406 INSP-Sprinkler Rough-in6/30/20146/30/20146/30/2014 3:21:43 PMPPASS
The underground supply piping is ok to cover
FIR14-00407 INSP-Sprinkler Rough-in6/30/20146/30/20146/30/2014 3:06:44 PMPPASS
Underground piping is ok to cover
FIR14-00197 INSP-Sprinkler Rough-in6/27/20146/30/20146/30/2014 3:03:06 PMAPASS
Forward flush passed, ceiling tile can be installed and pipe covered. Need to install sprinkler protection in the combustible concealed space above the exhaust hood.