FIR19-00292
| INSP-Sprinkler Rough-in | 6/4/2019 | 6/5/2019 | 6/5/2019 2:54:03 PM | P | PASS |
|
|
Rough-in passed. Call for access- Steve Phone #: ###-####
|
FIR19-00375
| INSP-Sprinkler Rough-in | 6/4/2019 | 6/5/2019 | 6/5/2019 2:39:12 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered. Contact Leroy Anderson ###-#### 30 min prior to RTC Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-00751
| FIRE-Sprinkler Rough-in | 6/5/2019 | 6/5/2019 | 6/5/2019 1:57:10 PM | P | CANC |
|
|
Wrong permit called in for the inspection type requested.
Contact Jim Hibbard for any questions Phone #: ###-#### Inspection requested via web by James Hibbard
|
FIR18-00856
| INSP-Final Inspection | 6/3/2019 | 6/5/2019 | 6/5/2019 12:27:26 PM | P | FAIL |
|
|
I called the contact number twice but could not leave a message due to voice mail being full. I went to the project site and spoke to school superintendant but did not make contact with the sprinkler contractor. No inspection performed.
Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR18-00916
| INSP-Sprinkler Rough-in/Hydro | 6/4/2019 | 6/5/2019 | 6/5/2019 12:20:28 PM | A | PART |
|
|
Overhead hydro witnessed with no loss on the guage. The earthquake attachments have been addressed. I discussed with Andrew the requirements for NFPA 20, A.4.15.6, 4.12.1.3, ball drip in the test header line and piping the relief valve
Contact Andrew Larson ###-#### 30 Min prior to Hydro Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-00195
| FIRE-Final Inspection | 6/5/2019 | 6/5/2019 | 6/5/2019 12:11:06 PM | P | PASS |
|
|
life safety passed
Phone #: ###-#### Inspection requested via web by Pat Churchman
|
BLD19-00193
| FIRE-Final Inspection | 6/4/2019 | 6/5/2019 | 6/5/2019 12:10:35 PM | A | PASS |
|
|
Life safety passed.
Phone #: ###-#### Inspection requested via web by Pat Churchman
|
FIR19-00080
| INSP-Final Inspection | 6/4/2019 | 6/5/2019 | 6/5/2019 10:33:10 AM | A | FAIL |
|
|
Plan mod needed for changing the hallway strobes to 30cd, need to show Mezzanine and Mechanical Room notification devices, need to test Gym duct smoke detectors and change two devices to weather proof. Need to witness notification testing.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00326
| INSP-Final Inspection | 6/4/2019 | 6/5/2019 | 6/5/2019 10:31:20 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Mick Woodburn
|
BLD19-00250
| FIRE-Final Inspection | 6/4/2019 | 6/5/2019 | 6/5/2019 9:36:07 AM | A | PART |
|
|
Life safety passed for units 137, 139, 238 and 329 // Gary Phone #: ###-####
|