Inspections for the day of: Friday, June 7, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02795 FIRE-Final Inspection6/7/20196/7/20196/7/2019 3:09:16 PMPFAIL
Provide sign offs for the project related fire sprinkler and fire alarm permits, Provide emergency light for the Fire Pump Room, Provide testing/inspection for the elevator, Provide singage for the Fire Pump/Riser Room.

Chad- Phone #: ###-####
GRD18-00064 FIRE-Final Inspection6/7/20196/7/20196/7/2019 3:07:20 PMPFAIL
Provide "No Parking Zone" at space i front of the north fire hydrant, Provide fire dept/plan review approval for modified fire dept access road.
BLD19-01995 FIRE-Final Inspection6/7/20196/7/20196/7/2019 1:57:07 PMPPASS
life safety passed

Call to meet // Gary Phone #: ###-####
FIR18-00809 INSP-Alarm Testing6/7/20196/7/20196/7/2019 1:26:12 PMPDONE
Need the interconnections with the fire sprinkler/fire pump devices tested, need elevator recall tested. Need duct smoke detectors tested. It appears the sync issue is actually an echo from the concrete floors and large open spaces.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR18-00916 INSP-Final Inspection6/6/20196/7/20196/7/2019 1:24:41 PMPCANC
Still need the underground supply line hydro passed and the valve added on the discharge side of the pump. Need devices tested with the Fire Alarm Control Panel.

Contact Andrew Larson ###-#### 30 min prior to fire final insp start please.

Thank you Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00913 INSP-Sprinkler Rough-in/Hydro6/6/20196/7/20196/7/2019 1:23:14 PMACANC
The underground supply piping is still losing pressure. Was not able to start a test.

Contact Andrew Larson ###-#### 30 min prior to UG Hydro start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF19-00034 INSP-Final6/6/20196/7/20196/7/2019 12:31:29 PMADONE
Life safety passed

Call prior to going Phone #: 4056425898 >> Inspection requested via mobile web by Michael
BLD19-00139 FIRE-Final Inspection6/6/20196/7/20196/7/2019 12:14:35 PMACANC
Will be ok to final life safety when the project related fire alrm permit has been finaled.

Troy,

Call me when you get a moment before you head over to the space.

Thanks,

Todd Phone #: ###-#### Inspection requested via web by Todd Kurns
FIR19-00239 INSP-Final Inspection6/7/20196/7/20196/7/2019 10:27:41 AMAPASS
Permit finaled.

mike oswald Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR19-00239 INSP-Sprinkler Rough-in6/7/20196/7/20196/7/2019 10:27:20 AMAPASS
mike oswald Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD18-04307 FIRE-Final Inspection6/6/20196/7/20196/7/2019 10:24:47 AMAFAIL
Provide fire extinguisher and emergency lighting as per the approved plans.

Kenny Phone #: ###-####
BLD19-00845 FIRE-Final Inspection6/6/20196/7/20196/7/2019 9:45:45 AMAPASS
Life safety passed

Requested by Shane Treasure Phone #: ###-#### Inspection requested via web by Shane Treasure
FIR19-00312 INSP-Final Inspection6/6/20196/7/20196/7/2019 9:45:06 AMAPASS
Permit finaled

Nick Phone #: ###-####
NAF19-00042 INSP-Final6/6/20196/7/20196/7/2019 9:22:37 AMADONE
Permit finaled. Suppression system function witnessed.

Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
FIR18-00809 INSP-Alarm Testing6/6/20196/7/20196/7/2019 8:12:16 AMACANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Friday, June 07, 2019.
NAF19-00042 INSP-Sprinkler Rough-in/Hydro6/6/20196/7/20196/6/2019 2:10:29 PMACANC
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson Inspection cancelled via mobile web on Thursday, June 06, 2019.
FIR18-00809 INSP-Alarm Testing6/6/20196/7/20196/6/2019 11:20:40 AMPCANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 06, 2019.