Inspections for the day of: Wednesday, July 10, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00397 INSP-Sprinkler Rough-in7/9/20197/10/20197/10/2019 1:52:40 PMPPASS
Rough-in passed for all areas except for the front lobby area where one additional pendant has been added. Either the pendant needs removed or plan mods are needed due to this being a remote area. Piping can be covered in all areas except this lobby area.

Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00267 INSP-Final Inspection7/10/20197/10/20197/10/2019 1:51:08 PMPFAIL
Not ready for final due to ceiling tile missing. But all piping can be covered. Today was for an ok on the electrical room.

Contact Hunter Anderson ###-#### 30 Min Prior to Final Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-00521 FIRE-Final Inspection7/10/20197/10/20197/10/2019 12:38:13 PMPFAIL
No small documents on site. I noted that one exit discharge light did not function and the other was not installed yet. We discussed CO alarm and occupant load signage. Fire extinguisher and hood suppression inspections are current. Per the contractor there was no change of kitchen equipment or change of hvac equipment.

Josh- please call before arriving Phone #: ###-####
BLD18-02261 FIRE-Final Inspection7/9/20197/10/20197/10/2019 11:30:47 AMAFAIL
I left voice message that I was on the way. I went to the school and wandered aroung the corridors but made no contact. I noted the fire alarm panel is in trouble. It appears notification has been bypassed. No inspection performed. I also noted that no sprinkler inspection had been scheduled.

Nick Phone #: ###-####
BLD18-02610 FIRE-Final Inspection7/9/20197/10/20197/10/2019 11:29:07 AMAFAIL
The new parapets have formed combustible concealed spaces as defined by NFPA 13 and need to be addressed as per NFPA 13. Per our conversation they will be filled with non-combustible insulation. This will need to be verified prior to a life safety sign off

contact Rick
have print and should be good to go Phone #: ###-#### Inspection requested via web by rick pew
FIR18-00572 INSP-Final Inspection7/9/20197/10/20197/10/2019 11:08:38 AMPCANC
Cancel per Kristin. Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00336 INSP-Final Inspection7/9/20197/10/20197/10/2019 11:08:15 AMPCANC
Cancel per Kristin. Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00267 INSP-Final Inspection7/10/20197/10/20197/10/2019 11:00:19 AMPCANC
Contact Perly Daniel ###-#### 30 min prior to Fire Final Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
BLD19-00488 FIRE-Final Inspection7/9/20197/10/20197/10/2019 7:27:59 AMAPASS
Life safety passed

Clint Phone #: ###-####
FIR19-00256 INSP-Final Inspection7/10/20197/10/20197/10/2019 7:27:20 AMAPASS
Permit finaled