FIR18-00139
| INSP-Sprinkler Rough-in/Hydro | 7/12/2018 | 7/12/2018 | 7/12/2018 2:34:10 PM | P | FAIL |
|
|
Underground hydro test failed due to visible loss on the guage.
Troy Phone #: ###-####
|
FIR17-00596
| INSP-Sprinkler Rough-in | 7/12/2018 | 7/12/2018 | 7/12/2018 1:52:46 PM | P | PASS |
|
|
Piping in the Office near the Sterile Corridor can be covered.
Contact Hunter Anderson ###-#### 30 min prior to RTC Insp Start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD17-00339
| FIRE-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 1:52:09 PM | P | FAIL |
|
|
Not ready for final yet. Need the sub permits taken care of
Ross Phone #: ###-####
|
NAF18-00010
| INSP-Final | 7/11/2018 | 7/12/2018 | 7/12/2018 1:51:25 PM | A | FAIL |
|
|
Need city approved plans on site, need to repair exit signs and place as shown on the plans, need to provide emergency lighting as discussed.
Call prior to going Phone #: 2088717466 >> Inspection requested via mobile web by Demo Newbold
|
BLD18-00301
| FIRE-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 12:32:16 PM | A | PASS |
|
|
life safety passed
Will Phone #: ###-####
|
FIR17-00412
| INSP-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 12:19:02 PM | P | FAIL |
|
|
Ceiling tile not installed yet. Interconnect with the fire alarm system was incorrect. Need forward flush test.
|
FIR18-00057
| INSP-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 12:18:40 PM | P | FAIL |
|
|
Ceiling tile not installed yet. Interconnect with the fire alarm system was incorrect. Need forward flush test.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR17-00683
| INSP-Final Inspection | 7/10/2018 | 7/12/2018 | 7/12/2018 12:13:13 PM | P | FAIL |
|
|
See city approved plans for audio/visual devices that are overspaced. Voice evac message is not functional in the new area or the existing gym. Tamper switches wired backwards. Devices are missing. Inspection stopped until all corrections have been made and system has been pre-tested.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
FIR18-00351
| INSP-Final Inspection | 7/12/2018 | 7/12/2018 | 7/12/2018 9:13:19 AM | A | PASS |
|
|
Permit finaled
|
NAF18-00061
| INSP-Sprinkler Rough-in | 7/10/2018 | 7/12/2018 | 7/12/2018 8:17:27 AM | A | PASS |
|
|
tenting in main corridor/verticals passed.Piping can be covered.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|