Inspections for the day of: Friday, July 13, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00339 FIRE-Hydro test above ground7/13/20187/13/20187/13/2018 3:48:16 PMPCANC
Duplicate inspection
FIR17-00412 INSP-Final Inspection7/12/20187/13/20187/13/2018 3:47:47 PMPPASS
permit finaled

. forward flush passed

Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-00339 FIRE-Final Inspection7/12/20187/13/20187/13/2018 3:46:28 PMPFAIL
Need all ceiling tile installed, Engineering Room complete (plan mod) and the project related fire alarm permit finaled. Per Ron Johnson a temporary will be ok when all of the ceiling tile has been installed


Ross is the super. Scheduling a final in the event our hardware and tile get done in time. We got approval to cover today. Also scheduled a conference to review as much as we can and then finish Monday if we have to. Thank you. Phone #: ###-#### Inspection requested via web by Jackie Phelps
BLD17-00339 FIRE-Conference7/12/20187/13/20187/13/2018 3:43:45 PMPPART
Fire life safety walk through - em lights, exit lights, egress lights, hardware and ceiling tile will be in progress for a final on Monday. Would like to get as much as we can looked at Friday and finish up Monday with the fire sprinkler contractor. (There is a chance we might achieve everything by Friday afternoon so will request a final as well) Phone #: ###-#### Inspection requested via web by Jackie Phelps
FIR18-00057 INSP-Final Inspection7/12/20187/13/20187/13/2018 3:42:50 PMPPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR17-00683 INSP-Final Inspection7/12/20187/13/20187/13/2018 3:42:25 PMPPART
Temporary being given until as-builts submitted/approved showing the address changes, deleting PIV and deleting tamper at the knox box.

Phone #: ###-#### Inspection requested via web by Gary Gambino
BLD17-04653 FIRE-Conference7/12/20187/13/20187/13/2018 12:59:23 PMPDONE
Conference was for direction on suppression requirements for 46 "woks" that are being installed. Fire suppression systems will be required as per IMC type 1 hood requirements and the manufactures/UL requirements.


Dave Phone #: ###-####
NAF18-00087 INSP-Sprinkler Rough-in/Hydro7/12/20187/13/20187/13/2018 11:09:56 AMPPART
General rough-in for overhead pipe passed. I noted in the Kitchen area the pendant is not placed as per plan and may be too close to the oven when installed. I noted in the Dining room the pendant head is too far off of the stair wall (8' max.) and the stair landing at this same location has no sprinkler protection. Plans have been marked in red at corrections. First ansnd second floor piping can be covered but third floor piping can not until a tenting inspection has been passed. Heads have not been verified (no ladder) and neither has the pump/riser. The riser piping will need to be steel due to the cpvc piping is not listed to be more than 1 1/2" from walls.

Call ahead to coordinate time, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00139 INSP-Sprinkler Rough-in/Hydro7/13/20187/13/20187/13/2018 10:59:52 AMPPASS
underground hydro test passed

- Troy Phone #: ###-####
NAF18-00061 INSP-Final7/13/20187/13/20187/13/2018 8:24:57 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Matthew Lewis
FIR17-00596 INSP-Sprinkler Rough-in7/12/20187/13/20187/13/2018 8:21:14 AMAPASS
The remaining piping can be covered.