FIR19-00448
| INSP-Final Inspection | 7/15/2019 | 7/16/2019 | 7/16/2019 4:55:17 PM | P | PASS |
|
|
Permit finaled. Inspection performed by Lee.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00336
| INSP-Final Inspection | 7/12/2019 | 7/16/2019 | 7/16/2019 3:57:05 PM | P | PASS |
|
|
Permit finaled. Inspection performed by Lee. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
NAF18-00096
| INSP-Conference | 7/16/2019 | 7/16/2019 | 7/16/2019 3:24:07 PM | P | DONE |
|
|
I spoke with the owners rep from texas about the exit sign over the blocked secondary exit.
|
FIR19-00440
| INSP-Supply line flush | 7/16/2019 | 7/16/2019 | 7/16/2019 3:15:42 PM | P | PASS |
|
|
All underground supply piping is ok for cover except the two 90's which still need thrust blocks poured.. This inspection is for underground cover. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR18-00886
| INSP-Sprinkler Rough-in | 7/15/2019 | 7/16/2019 | 7/16/2019 2:17:44 PM | P | CANC |
|
|
Contact Noemi Carrero ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
BLD19-01077
| FIRE-Final Inspection | 7/12/2019 | 7/16/2019 | 7/16/2019 1:51:36 PM | P | FAIL |
|
|
Inspection was just for the south half of the second floor at this time. Basically all exit signs need repaired and emergency lighting provided in the remodeled tenant space and in the paths of egress down both stair wells and out of the building. All other items for this phase of the work appear ok.
Please call 30 mins ahead of time Phone #: ###-#### Inspection requested via web by Gerome Fries
|
NAF19-00065
| INSP-Sprinkler Rough-in/Hydro | 7/16/2019 | 7/16/2019 | 7/16/2019 1:12:41 PM | P | CANC |
|
|
Conact: Leon Taylor Phone #: ###-#### >> Inspection requested via web by Hunter Fillmore Inspection cancelled from web by: Hunter Fillmore
|
FIR19-00281
| INSP-Sprinkler Rough-in | 7/15/2019 | 7/16/2019 | 7/16/2019 9:42:36 AM | A | PASS |
|
|
Piping is ok for cover except for Room 501. Can not use the small room rule since the room exceeds 800 sq. ft.
Contact Tanner Loomis ###-#### 30 Min prior to RTC Insp - Please enter off the Milwaukee St entrance of bldg for inspection.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-01437
| FIRE-Final Inspection | 7/15/2019 | 7/16/2019 | 7/16/2019 9:41:46 AM | A | PASS |
|
|
Life safety passed.
Loyd- please call 30min ahead before arriving Phone #: ###-####
|
FIR18-00572
| INSP-Final Inspection | 7/12/2019 | 7/16/2019 | 7/16/2019 12:00:00 AM | P | CANC |
|
|
cancel at 1:35pm on 7/16/19 by Kristen Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
|