BLD18-00902
| FIRE-Final Inspection | 6/29/2018 | 7/2/2018 | 7/2/2018 3:07:28 PM | A | FAIL |
|
|
The storage racks have been modified so that they do not exceed 8'. I let chad know that they can not exceed 12' in height for storage without a High Pile Storage permit. I am still waiting for fire dept approval for the calculations for the bollards at the nitrogen tank. Also the electrical dept has requested that life safety not be signed off until the required electrical permits are issued for the work that has been performed.
Chad Phone #: ###-####
|
BLD17-01656
| FIRE-Final Inspection | 6/29/2018 | 7/2/2018 | 7/2/2018 2:08:35 PM | P | FAIL |
|
|
Provide exit signs/repair exit signs as shown on the city approved plans, provide annual inspection for the expired fire extinguishers, provide plan review approval of the door hardware/door swing in the new areas.
Jack Phone #: ###-####
|
BLD18-01180
| FIRE-Final Inspection | 6/29/2018 | 7/2/2018 | 7/2/2018 2:08:18 PM | P | FAIL |
|
|
Provide exit signs/repair exit signs as shown on the city approved plans, provide annual inspection for the expired fire extinguishers, provide plan review approval of the door hardware/door swing in the new areas.
Jack Phone #: ###-####
|
FIR18-00387
| INSP-Final Inspection | 7/2/2018 | 7/2/2018 | 7/2/2018 12:51:44 PM | P | PASS |
|
|
Permit finaled
|
FIR18-00386
| INSP-Final Inspection | 7/2/2018 | 7/2/2018 | 7/2/2018 12:51:25 PM | P | PASS |
|
|
Permit finaled
|