Inspections for the day of: Friday, July 20, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00822 INSP-Final Inspection7/20/20187/20/20187/20/2018 2:46:51 PMPFAIL
I need to verify as-builts match installation, both vents on the fire pump fuel tank need to vent to the exterior of the building as per NFPA 20 and IFC requirements.

Mike Martin is the contact for this final inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-01975 FIRE-Final Inspection7/20/20187/20/20187/20/2018 1:48:55 PMPFAIL
Need the project related fire alarm permit finaled. Life safety looks ok when that work is done.


Early afternoon - Bob Phone #: ###-####
BLD18-01310 FIRE-Final Inspection7/17/20187/20/20187/20/2018 1:13:18 PMPPASS
Life safety passed

You can call Jim Carriveau if you have any issues ###-####. Aloha! Phone #: ###-#### Inspection requested via web by Colyn Levandoske
FIR15-00822 INSP-Final Inspection7/16/20187/20/20187/20/2018 12:37:19 PMAFAIL
Pump commissioning passed. Need as-builts of the fire pump assembly as discussed, need approval from the fire dept on the fuel tank venting. Need signage on the fire pump room door. Need all of the fire alarm interconnections tested.

Phone #: ###-#### Inspection requested via web by Stan Beus
NAF18-00049 INSP-Final7/18/20187/20/20187/20/2018 12:35:19 PMPFAIL
Not ready for final. Still need hydro test for the new piping in the Kitchen and the ceiling tile needs to be removed so that a rough-in inspection can be done for the sprinkler piping in the Kitchen. Need ceiling tile installed in the clouds in the Dining area and all of the upright sprinklers in the Dining need the covers off the sprinklers.

Call prior to going Phone #: 2088903587 >> Inspection requested via mobile web by Raul Munoz
BLD17-01088 FIRE-Final Inspection7/19/20187/20/20187/20/2018 11:43:48 AMAFAIL
Need project related fire alarm permit finaled and an exit sign added in new corridor.


Barry Phone #: ###-####
FIR17-00364 INSP-Final Inspection7/19/20187/20/20187/20/2018 11:43:13 AMAFAIL
Need as-builts, need smoke detector in existing corridor, need additional strobe in Pharmacy.

Rafe Phone #: ###-####
FIR17-00596 INSP-Final Inspection7/19/20187/20/20187/20/2018 11:41:25 AMAPASS
Permit finaled
BLD18-02294 FIRE-Final Inspection7/19/20187/20/20187/20/2018 9:55:11 AMAPASS
Life safety passed. Racking has been modified to not exceed 8'

call 15 mins ahead- Lisa Phone #: ###-####
BLD17-02156 FIRE-Final Inspection7/19/20187/20/20187/20/2018 7:50:07 AMAPASS
Life safety passed. Fire dept verified gate function

Bruce Phone #: ###-####
NAF18-00049 INSP-Final7/18/20187/20/20187/18/2018 10:22:20 AMPCANC
Call prior to going Phone #: 2088706532 >> Inspection requested via mobile web by Roy Fouts Inspection cancelled via mobile web on Wednesday, July 18, 2018.