FIR13-00686
| FIR-Aging Inspection | 7/25/2017 | 7/25/2017 | 7/25/2017 2:45:27 PM | | NR |
|
|
Left message for Colton requesting follow up.
|
FIR13-00545
| FIR-Aging Inspection | 7/25/2017 | 7/25/2017 | 7/25/2017 2:42:16 PM | | NR |
|
|
Per Rose this work should be completed next month and a final inspection scheduled
|
BLD17-00931
| FIRE-Final Inspection | 7/25/2017 | 7/25/2017 | 7/25/2017 2:36:09 PM | P | CANC |
|
|
Drawings not available.
pat Phone #: ###-####
|
FIR17-00304
| INSP-Final Inspection | 7/25/2017 | 7/25/2017 | 7/25/2017 2:06:05 PM | P | PASS |
|
|
Permit finaled
|
BLD17-01639
| FIRE-Final Inspection | 7/25/2017 | 7/25/2017 | 7/25/2017 1:30:57 PM | P | FAIL |
|
|
Provide exit signs/emergency lighting in the Conference Room and panic hardware at the back exit as per the approved plans.
|
BLD17-00214
| FIRE-Final Inspection | 7/24/2017 | 7/25/2017 | 7/25/2017 11:05:02 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Richard Wilson Inspection cancelled from web by: Richard Wilson
|
FIR16-00821
| INSP-Sprinkler Rough-in | 7/25/2017 | 7/25/2017 | 7/25/2017 10:41:37 AM | P | PASS |
|
|
The two combustible concealed spaces at the restrooms have been filled with insulation and an additional head at the movable partion wall is approved for cover. This work was in the west most building.
|
BLD17-00545
| FIRE-Final Inspection | 7/24/2017 | 7/25/2017 | 7/25/2017 10:33:20 AM | A | PASS |
|
|
Life safety passed
|
BLD17-00107
| FIRE-Final Inspection | 7/24/2017 | 7/25/2017 | 7/25/2017 10:00:58 AM | A | FAIL |
|
|
Exit discharge light needs repaired and per IFC 904.3.4 and plan review, notificaton is required in this new room/area due to the existing suppression system in the existing area. Permit is required.
|
BLD17-01528
| FIRE-Final Inspection | 7/24/2017 | 7/25/2017 | 7/25/2017 8:55:36 AM | A | FAIL |
|
|
Provide re-certification of both hood suppression systems, repair/install all exit signs/emergency lights/exit discharge lights and provide testing, provide tagged fire extinguishers per plans and discussion, provide occupant load sign, provide data sheet verifying the restroom doors meet ADA, blank keyed dead bolt to Play Land.
|
FIR16-00806
| INSP-Final Inspection | 7/24/2017 | 7/25/2017 | 7/25/2017 8:12:31 AM | A | PASS |
|
|
Permit finaled
|