Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00686 FIR-Aging Inspection7/25/20177/25/20177/25/2017 2:45:27 PM NR
Left message for Colton requesting follow up.
FIR13-00545 FIR-Aging Inspection7/25/20177/25/20177/25/2017 2:42:16 PM NR
Per Rose this work should be completed next month and a final inspection scheduled
BLD17-00931 FIRE-Final Inspection7/25/20177/25/20177/25/2017 2:36:09 PMPCANC
Drawings not available.


pat Phone #: ###-####
FIR17-00304 INSP-Final Inspection7/25/20177/25/20177/25/2017 2:06:05 PMPPASS
Permit finaled
BLD17-01639 FIRE-Final Inspection7/25/20177/25/20177/25/2017 1:30:57 PMPFAIL
Provide exit signs/emergency lighting in the Conference Room and panic hardware at the back exit as per the approved plans.
BLD17-00214 FIRE-Final Inspection7/24/20177/25/20177/25/2017 11:05:02 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Richard Wilson Inspection cancelled from web by: Richard Wilson
FIR16-00821 INSP-Sprinkler Rough-in7/25/20177/25/20177/25/2017 10:41:37 AMPPASS
The two combustible concealed spaces at the restrooms have been filled with insulation and an additional head at the movable partion wall is approved for cover. This work was in the west most building.
BLD17-00545 FIRE-Final Inspection7/24/20177/25/20177/25/2017 10:33:20 AMAPASS
Life safety passed
BLD17-00107 FIRE-Final Inspection7/24/20177/25/20177/25/2017 10:00:58 AMAFAIL
Exit discharge light needs repaired and per IFC 904.3.4 and plan review, notificaton is required in this new room/area due to the existing suppression system in the existing area. Permit is required.
BLD17-01528 FIRE-Final Inspection7/24/20177/25/20177/25/2017 8:55:36 AMAFAIL
Provide re-certification of both hood suppression systems, repair/install all exit signs/emergency lights/exit discharge lights and provide testing, provide tagged fire extinguishers per plans and discussion, provide occupant load sign, provide data sheet verifying the restroom doors meet ADA, blank keyed dead bolt to Play Land.
FIR16-00806 INSP-Final Inspection7/24/20177/25/20177/25/2017 8:12:31 AMAPASS
Permit finaled